User Manual 

V1.0.1

 

 

Summary of Contents for cMT CTRL01

Page 1: ...User Manual V1 0 1...

Page 2: ...ory 9 2 3 5 Email 10 2 3 6 Project Management 10 2 3 7 System Password 11 2 3 8 Enhanced Security 11 2 3 9 EasyAccess 2 0 Optional 12 2 3 10 OPA UA 12 2 3 11 Communication 12 Updating Web Package and...

Page 3: ...Project 36 Chapter9 9 1 Creating Tags 36 9 2 Exporting Tags 36 9 3 Configuring EasyBuilder 37 Connecting cMT CTRL01 CODESYS to iR Series Modules 38 Chapter10 Connecting cMT CTRL01 to iR ETN 41 Chapte...

Page 4: ...AN 1 10 100 1000 Base T x 1 LAN 2 10 100 Base T x 1 COM Port COM1 RS 232 2W COM2 RS 485 2W 4W COM3 RS 485 2W Local bus iBus CAN Bus N A RTC Built in Power Input Power 24 20 VDC Power Isolation Built i...

Page 5: ...RUN STOP switch e LAN 1 b Reset Button f LAN 2 c COM1 RS 232 COM2 RS 485 2W 4W COM3 RS 485 2W g SD Card Slot d Power Connector h Expansion Connector 81mm 3 19 109mm 4 29 50mm 1 97 a b c d f e g h Top...

Page 6: ...of time button is pressed ERR LED Action 0 3 seconds No action 3 10 seconds Blinking Reboot PLC and Gateway Over 10 seconds Lights UP Reset to default The projects stored in the unit will be cleared...

Page 7: ...0 3V lithium battery to keep the RTC running Battery Specification UL Certification Battery Type CR1220 Rated 3V Max Abnormal Charging Current 10mA Working Temperature max 70 C Battery replacement sha...

Page 8: ...16 N 130mA 0 65 W iR DQ08 R 220mA 1 1 W iR DQ16 N 205mA 1 02 W iR DQ16 P 196mA 0 984 W iR DI16 K 83mA 0 418 W Analog I O iR AQ04 VI 65mA 0 325 W iR AI04 VI 70mA 0 35 W iR AM06 VI 70mA 0 35 W iR AI04 T...

Page 9: ...select a function from Reboot Download or Upload cMT CTRL01 can be found in the IP HMI Name group box by using the model s IP address even if the PC or laptop is not on the same network UtilityManage...

Page 10: ...Login page and the language used can be changed in this page Icon Description Displays HMI name Displays system date Displays system time Please note that by default LAN 2 is assigned for Gateway DHC...

Page 11: ...teway and DNS cMT CTRL01 is equipped with dual Ethernet ports that can be freely assigned as one of the following 1 One Ethernet port for CODESYS LAN1 DHCP and the other one for IIoT Gateway LAN2 DHCP...

Page 12: ...dentification light The LED indicator of the unit will flash three times when this button is clicked helping user to find the unit 2 3 4 History This tab offers settings related to historical data Cle...

Page 13: ...P Configure email server and relevant settings Contacts Set email contacts in this tab Update Email Contacts Import the email contacts built using Administrator Tools 2 3 6 Project Management This tab...

Page 14: ...in the external device to update the project file on cMT CTRL01 2 3 7 System Password Set login password and the password for transferring project file 2 3 8 Enhanced Security The account settings in...

Page 15: ...more information on EasyAccess 2 0 please see EasyAccess 2 0 User Manual 2 3 10 OPA UA Configure OPC UA settings Please see Chapter 6 OPC UA Web Management Interface in this manual for details 2 3 11...

Page 16: ...cMT CTRL01 User Manual V1 0 1 13...

Page 17: ...device connected via COM port Interface Baud rate Data Bits Parity Stop Bits Timeout Parameter 1 Parameter 2 Send ACK Delay Parameters that can be viewed and modified for a device connected via Ethern...

Page 18: ...age and OS can be updated through Ethernet Launch Utility ManagerEX select Gateway Series Maintenance cMT Gateway OS Update 3 1 Updating Web Package 1 Select an HMI to update OS 2 Select Web package a...

Page 19: ...sage carefully before you click OK 3 If you click OK the cMT Gateway OS Update window opens again browse for the source file and then click Update 4 The message window below opens please do not turn o...

Page 20: ...cMT CTRL01 User Manual V1 0 1 17...

Page 21: ...asic steps are 1 Add a driver into Device List in EasyBuilder Pro 2 Enable OPC UA Server and designate communication address 3 Download the project to HMI The following explains how to set up OPC UA S...

Page 22: ...New Tag to add tags monitored using OPC UA When finished click OK to leave Step 5 Find the created tags in OPC UA Server window When a large number of tags are used the tags can be exported as a csv e...

Page 23: ...Project Download PC HMI and set HMI IP address The project can be downloaded via Ethernet Way 2 Download using website Open internet browser IE Chrome Firefox enter cMT CTRL01 s IP address e g 192 168...

Page 24: ...se see OPC UA server manual 4 4 On line Off line Simulation Running On line or Off line simulation in EasyBuilder Pro helps you examine OPC UA Tag settings In On line simulation cMT Gateway Viewer can...

Page 25: ...cMT CTRL01 User Manual V1 0 1 22 Step 3 In On line Simulation data in PLC tags will also change...

Page 26: ...UserManual_en pdf Modbus TCP IP Gateway OPC UA Client MQTT Server MQTT Subscriber MQTT Publisher Administrator Tools Time synchronization NTP Macro Project protection iE XE eMT mTV communication proto...

Page 27: ...into the address bar of a web browser At the entry page log in with System setting s password Factory default of the password is 111111 Suggested resolution 1024 768 or higher Navigate to the OPC UA c...

Page 28: ...ctive client connection when shutting down the server will wait for a few seconds before closing off completely In addition both the toggle button and a line of text also indicate the status of the se...

Page 29: ...trust the certificate from any client connection OPC UA server must be configured with at least one user authentication mode as listed in the following table Authentication Descriptions Anonymous Allo...

Page 30: ...y available in the OPC UA server New nodes and groups can be added while existing nodes and groups can be edited or deleted For ease of navigation detail information of the currently selected node gro...

Page 31: ...ll Free Tag Names Siemens S7 1200 1500 Symbolic Addressing etc 6 5 Certificates In this page the user can manage certificates and revocation lists of the OPC UA server Use the dropdown menu to access...

Page 32: ...e generated automatically if own certificate is absent when server starts up Trusted Client Issuers List of trusted client issuer certificates Supported operation Import Remove Export Trusted User Iss...

Page 33: ...take effect 6 7 Advanced Additional settings can be configured in the Advanced tab The user can set the trace logging level and specific startup behavior of the OPC UA server Furthermore the trace lo...

Page 34: ...Package file we prepared and follow these steps for quick installation 1 First get a copy of CODESYS Package file 2 On your PC right click the mouse button and select Open with CODESYS Package Manager...

Page 35: ...cMT CTRL01 User Manual V1 0 1 32 5 The installed component will be shown in the installation summary...

Page 36: ...irefox Safari enter cMT CTRL01 s IP address e g 192 168 100 1 and then configure cMT CTRL01 settings 3 Open CODESYS page to see the IP address By default DHCP is used for cMT CTRL01 CODESYS IP 8 2 Cre...

Page 37: ...ilt in CODESYS to open the settings window 4 Open Scan Network tab CODESYS software will start searching for the CODESYS devices on the same network Select the desired device and then click OK to leav...

Page 38: ...cMT CTRL01 User Manual V1 0 1 35 5 The project will connect the selected device IP address of the device can be entered in the field shown below...

Page 39: ...everal tags in PLC_PRG tab and make tag test accumulate automatically 9 2 Exporting Tags 1 Right click on Application in Devices tree and then select Add Object Symbol Configuration use defaults 2 Fin...

Page 40: ...SYS in the device list 2 Open Tag Manager and click and then click Import Tag to import the xml file built in preceding steps 3 The CODESYS tags can now be found in Tag Manager 4 Create a Numeric obje...

Page 41: ...dules Chapter10 1 Right click on iBus iBus and then select Add Device 2 Select an iR module and then click Add Device 3 The added device can be found under iBus You may add more modules with this wind...

Page 42: ...us has two addresses in BYTE type that show low voltage and I O error 5 Open PLC_PRG in Devices tree and configure variables as shown below 6 In Devices tree double click on an iR module name to open...

Page 43: ...cMT CTRL01 User Manual V1 0 1 40 7 When finished click Online Login to download the project to CODESYS...

Page 44: ...be found in Devices tree 4 Double click on Ethernet with the current window opened in Devices tree or right click on Ethernet and then select Add Device 5 Click Fieldbusses Modbus Modbus TCP Master M...

Page 45: ...e Operating System Settings When Use operating System Settings is selected settings on cMT CTRL01 will be used without being changed 9 When CODESYS is already connected go to General tab and click the...

Page 46: ...cMT CTRL01 User Manual V1 0 1 43 11 Open Modbus Slave Channel tab and create Modbus Variable 12 Open PLC_PRG in Devices tree create tag and set Bool as data type Write a command as shown below...

Page 47: ...ay cMT CTRL01 supports Modbus TCP IP Gateway which allows CODESYS to access Modbus TCP IP Gateway using Modbus TCP Slave in order to control the devices connected to Modbus TCP IP Gateway On cMT CTRL0...

Page 48: ...read When setting Modbus Slave Channel Cycle Time can be configured to adjust the frequency at which data is written to the registers For more information on Modbus Gateway please see EasyBuilder Pro...

Page 49: ...V1 0 1 46 Removing Weintek Built in CODESYS Chapter12 1 Click Tools Packages Manager 2 Find Weintek Built in CODESYS and then click Uninstall 3 Click Next when seeing the window below 4 Removing the...

Page 50: ...cMT CTRL01 User Manual V1 0 1 47...

Page 51: ...installed its indicator will light up in red Please try the following 3 methods to solve this situation 1 Click the icon of CODESYS Gateway SysTray in system settings and then click Start Gateway 2 A...

Page 52: ...firmware 1 Launch Utility Manager and select cMT Series Maintenance CODESYS Firmware Update Browse for the firmware file and click Update 2 Enter cMT HMI s IP address in the website browser and find...

Page 53: ...cMT CTRL01 User Manual V1 0 1 50 2 Enter cMT HMI s IP address in the website browser and find CODESYS Project update tab Select the files generated in the previous step and click Update...