Weil-McLain WM2AC13018 Installer'S Information Manual Download Page 6

Page 6 

 

Installer’s Information Manual 

 

5. 

Be sure to ground the condensing unit by securing the 
ground  wire  to  the  grounding  lug  inside  the  control 
box. 

6. 

Be sure to follow National Electrical Code and all local 
codes 

NOTE:  Use copper conductors only. 

 

  CAUTION:    Casing  or  cabinet  must  be 

permanently grounded in accordance with National Electric 
Code or other applicable local codes. 

SECTION 6.  REFRIGERANT 
CHARGE 

Condensing units are supplied with a refrigerant charge (R-
22)  sufficient  for  typical  matching  evaporator  and 
approximately 

25 

feet 

of 

interconnecting 

tubing.  

Condensing  unit  liquid  and  suction  valves  are  closed  to 
contain the charge within the unit. 

MEASUREMENT 

If a calibrated charging cylinder or accurate weighing device 
is available, add refrigerant accordingly. 

 

  CAUTION:    Refrigerant  charging  should  only  be 

carried out by a qualified air conditioning contractor. 

FIELD CHARGING 

Depending on the type of restricting device that is installed 
on  the  system  (TXV,  piston,  capillary  tubes,  etc.),  the 
subcooling  or  superheat  charging  method  can  be  used  for 
field charging or checking the existing refrigerant charge in 
a system.  Because each installation is different in terms of 
indoor  air  flow,  refrigerant  line  length,  and  duct  variations, 
etc.,  the  factory  charge  may  not  be  correct  for  every 
application.    To  assure  the  best  performance  from  the  air 
conditioner,  the  refrigerant  charge  should  be  checked  and 
adjusted when needed on each installation. 

 

  CAUTION:    Compressor  damage  will  occur  if 

system is improperly charged.  On new system installations, 
charge  the  system  per  refrigerant  charge  information  label 
and follow guidelines in these instructions. 

 

  WARNING:  Refrigerant is under pressure.  Guard 

against refrigerant spraying into the face or on skin.  Always 
wear  protective  equipment,  i.e.  safety  glasses  or  goggles 
and gloves when working with refrigerant. 

 

SUBCOOLING CHARGING METHOD 

The  subcooling  charging  method  is  to  be  used  on  units 
which  have  Thermostatic  Expansion  Valve  (TXV)  as  the 
expansion  device.    For  proper  subcooling  readings,  a 
standard high side gauge is required for pressure readings. 

1.  Measure the outdoor air temperature. (T1) 

2.  Measure  the  liquid  line  pressure  at  the  outdoor  unit 

and  determine  condenser  refrigerant  temperature  by 
the scale on the high side pressure gauge. (T2) 

3.  Measure the liquid line temperature on the liquid line at 

the outdoor unit. (T3) 

4.  Subtract  T3  from  T2.  (T2  – T3)  This  is  the  subcooling 

value.    Compare  this  value  and  the  outdoor 
temperature (T1), to the chart on page 8 (Figure 3).  If 
the value is below the line, add refrigerant.  If the value 
is above the line, remove refrigerant charge. 

NOTE:    When  removing  refrigerant,  always  use  standard 
reclaim procedures. 

NOTE:  On  cooler  days  (65degF  or  lower),  attempts  to 
operate  the  air  conditioner  and  take  gauged  pressure 
readings may be unsuccessful, as unusually low pressures 
will be observed on the suction line.  This type of operation 
may give the impression of an undercharged unit.  Such is 
NOT necessarily the case.  The low-pressure reading may 
exist because of the large condenser surface area and the 
cold  ambient  air  removing  so  much  heat  from  the 
refrigerant.    Sub-cooling  occurs  and  results  in  very  low 
pressures.  Adding refrigerant in cold  weather  will result in 
an  overcharged  unit,  which  may  then  trip  out  on  high 
pressure limit during warm or hot weather.  Line pressures 
should  not  be  taken  for  test  purposes  when  the  outdoor 
temperature  is  below  70degF  since  a  false  reading  may 
occur.    Do  not  attempt  to  operate  the  air  conditioner  on  a 
day of 45degF or cooler. 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for WM2AC13018

Page 1: ...sted above You should become familiar with these instructions as it will be helpful in avoiding any needless service costs or operational problems Keep these instructions as long as you keep your equipment for future reference If any of the documents are missing or illegible contact your installer or equipment manufacturer for replacement Throughout this manual when we use the word you we refer to...

Page 2: ...ation work should begin until this inspection is completed The manufacturer assumes no responsibility for installation of incorrectly shipped units To alert you to potential hazards we use the signal words WARNING and CAUTION throughout this manual WARNING alerts you to situations that could cause or result in serious injury or death CAUTION alerts you to situations that could cause or result in m...

Page 3: ......

Page 4: ...holes in the base pan must be kept clear 12 Clearance around unit 18 Clearance for Service Area 60 Clearance Above Unit To Indoor Coil NEC Class 1 Wiring Power Supply NEC Class 2 Wiring Thermostat To Indoor Air Handler or Furnace Figure 2 Typical Location and Clearances SECTION 4 REFRIGERANT PIPING CONNECTIONS Undersized line sets will increase the refrigerant pressure drop between the indoor evap...

Page 5: ......

Page 6: ...t is under pressure Guard against refrigerant spraying into the face or on skin Always wear protective equipment i e safety glasses or goggles and gloves when working with refrigerant SUBCOOLING CHARGING METHOD The subcooling charging method is to be used on units which have Thermostatic Expansion Valve TXV as the expansion device For proper subcooling readings a standard high side gauge is requir...

Page 7: ...he system in operation check the condensing unit for unusual noise and undue vibration 5 Allow the system to operate until it is balanced or stabilized approximately 30 minutes before making further checks 6 Remove manifold gage hoses and install cap on Schrader valves SECTION 8 MAINTENANCE CAUTION Be sure the unit disconnect is in the OFF position and that all electrical power to the unit is turn...

Page 8: ...l Subcooling Chart for units with Thermostatic Expansion Valves 4 6 8 10 12 14 16 18 60 65 70 75 80 85 90 95 100 105 110 115 OUTDOOR TEMPERATURE deg F SUBCOOLING deg F Remove Refrigerant Add Refrigerant Figure 3 Subcooling Charging Chart ...

Page 9: ...ncorrect voltage Defective overload protector Refrigerant undercharge At compressor terminals voltage must be 10 of nameplate marking when unit is operating Replace check for correct voltage Add refrigerant High head pressure Low suction pressure Restriction in liquid line expansion device or filter drier Lack of sufficient indoor airflow Remove or replace defective component Clean check filters r...

Reviews: