Weil-McLain WM2AC13018 Installer'S Information Manual Download Page 4

Page 4 

 

Installer’s Information Manual 

A minimum clearance of 18 inches is required for service at 
the  control  panel  access.    A  12  inch  clearance  is  required 
for  the  air  inlet  to  the  outdoor  coil  around  the  perimeter  of 
the  unit.    The  air  discharge  of  the  unit  requires  a  60  inch 
clearance  between  the  top  of  the  unit  and  any  obstruction.  
See Figure 2. 

The  length  of  the  refrigerant  tubing,  between  the  outdoor 
unit and indoor coil, should be as short as possible to avoid 
capacity  and  efficiency  loss.    Excessive  spacing  of  the 
outdoor unit from the home can lead to the refrigerant lines 
being restricted by trampling or by being punctured by lawn 
mowers.    Locate  the  outdoor  unit  away  from  bedroom 
windows  or  other  rooms  where  sound  might  not  be 
desirable. 

Provide sufficient clearance from shrubs to  allow  adequate 
air  to  pass  across  the  outdoor  coil  without  leaves  or 
branches being pulled into the coil. 

Consideration  should  be  given  to  the  distance  and  routing 
of  electrical  service  that  would  have  to  be  run  to  connect 
the outdoor unit. 

The outdoor unit may be installed at ground level on a solid 
base  that  will  not  shift  or  settle,  causing  strain  on  the 
refrigerant  lines  and  possible  leaks.    Isolate  the  base  from 
the  structure  to  avoid  noise  or  vibration  transmission.  
When installing units on a roof, a structure should be used 
to  minimize  the  transmission  of  sound  or  vibration  into  the 
conditioned  space.    Thought  should  be  given  to  water 
drainage  away  from  the  outdoor  unit.    Drain  holes  in  the 
base pan must be kept clear.  

12" Clearance

around unit

18" Clearance

for Service Area

60" Clearance 

Above Unit

To Indoor Coil

NEC Class 1 

Wiring

Power 
Supply

NEC Class 2

Wiring

Thermostat

To Indoor Air Handler 
or Furnace

Figure 2.  Typical Location and Clearances 

SECTION 4.  REFRIGERANT PIPING 
CONNECTIONS 

Undersized  line  sets  will  increase  the  refrigerant  pressure 
drop  between  the  indoor  evaporator  and  outdoor  unit, 
resulting in a decrease in system capacity.  Over sizing the 
line sets may result in excessive refrigerant charge, thereby 
making  the  system  more  susceptible  to  liquid  migration.  
Slope horizontal vapor lines at least 1” every 20 feet toward 
the outdoor unit to facilitate proper oil return. 

Use only refrigerant grade (dehydrated and sealed) copper 
tubing  of  the  size  indicated  in  Table  1  to  interconnect  the 
condensing unit  with the indoor evaporator.   Take extreme 

care  to  keep  the  refrigerant  tubing  clean  and  dry  prior  to 
and during installation.  All outdoor unit and evaporator coil 
connections  are  copper  to  copper  and  should  be  brazed 
with  a  phosphorous-copper  alloy  material  such  as  Silfos-5 
or equivalent instead of soft solder.  The outdoor units have 
re-usable  service  valves  on  both  the  liquid  and  vapor 
connections.    Precautions  should  be  taken  to  prevent  heat 
damage to the valve by wrapping a wet rag around it when 
brazing. 

Do not remove plugs from ends of tubing until connection is 
ready  to  be  made.    Suction  line  insulation  is  necessary  to 
prevent  condensation  from  forming  on  and  dropping  from 
suction line.  Apply suction line insulation by sliding it on the 
sealed tubing before cutting and making connections.  See 
Table 1 for correct vapor line size. 

Summary of Contents for WM2AC13018

Page 1: ...sted above You should become familiar with these instructions as it will be helpful in avoiding any needless service costs or operational problems Keep these instructions as long as you keep your equipment for future reference If any of the documents are missing or illegible contact your installer or equipment manufacturer for replacement Throughout this manual when we use the word you we refer to...

Page 2: ...ation work should begin until this inspection is completed The manufacturer assumes no responsibility for installation of incorrectly shipped units To alert you to potential hazards we use the signal words WARNING and CAUTION throughout this manual WARNING alerts you to situations that could cause or result in serious injury or death CAUTION alerts you to situations that could cause or result in m...

Page 3: ......

Page 4: ...holes in the base pan must be kept clear 12 Clearance around unit 18 Clearance for Service Area 60 Clearance Above Unit To Indoor Coil NEC Class 1 Wiring Power Supply NEC Class 2 Wiring Thermostat To Indoor Air Handler or Furnace Figure 2 Typical Location and Clearances SECTION 4 REFRIGERANT PIPING CONNECTIONS Undersized line sets will increase the refrigerant pressure drop between the indoor evap...

Page 5: ......

Page 6: ...t is under pressure Guard against refrigerant spraying into the face or on skin Always wear protective equipment i e safety glasses or goggles and gloves when working with refrigerant SUBCOOLING CHARGING METHOD The subcooling charging method is to be used on units which have Thermostatic Expansion Valve TXV as the expansion device For proper subcooling readings a standard high side gauge is requir...

Page 7: ...he system in operation check the condensing unit for unusual noise and undue vibration 5 Allow the system to operate until it is balanced or stabilized approximately 30 minutes before making further checks 6 Remove manifold gage hoses and install cap on Schrader valves SECTION 8 MAINTENANCE CAUTION Be sure the unit disconnect is in the OFF position and that all electrical power to the unit is turn...

Page 8: ...l Subcooling Chart for units with Thermostatic Expansion Valves 4 6 8 10 12 14 16 18 60 65 70 75 80 85 90 95 100 105 110 115 OUTDOOR TEMPERATURE deg F SUBCOOLING deg F Remove Refrigerant Add Refrigerant Figure 3 Subcooling Charging Chart ...

Page 9: ...ncorrect voltage Defective overload protector Refrigerant undercharge At compressor terminals voltage must be 10 of nameplate marking when unit is operating Replace check for correct voltage Add refrigerant High head pressure Low suction pressure Restriction in liquid line expansion device or filter drier Lack of sufficient indoor airflow Remove or replace defective component Clean check filters r...

Reviews: