Weil-McLain SVF 1500-3000 Series User'S Information Manual Download Page 13

SVF

 

Series 1

 

Commercial Condensing Gas-Fired Water Boiler

 - User’s Information Manual

13

Part number 550-100-251/0819

Maintenance procedures — MONTHLY

Perform DAILY procedures plus the 

following additional procedures . . .

Check vent piping

Visually inspect the flue gas vent piping for any signs of blockage, 

leakage or deterioration of the piping. Notify your qualified service 

technician at once if you find any problem.

Failure to inspect the vent system as noted above and 

have it repaired by a qualified service technician can 

result in vent system failure, causing severe personal 

injury or death.

Check air piping 
(DIRECT VENT installations)

1.  Visually inspect the air inlet to be sure it is unobstructed. Inspect 

entire length of air piping to ensure piping is intact and all joints 

are properly sealed.

2.  Call your qualified service technician if you notice any problems.

Check the relief valve

1.  Inspect the boiler relief valve and the relief valve discharge pipe 

for signs of weeping or leakage.

2.  If the relief valve often weeps, the expansion tank may not be 

working properly. Immediately contact your qualified service 

technician to inspect the boiler and system.

Check the condensate drain system

1.  While the boiler is running, check the discharge end of the 

condensate drain tubing by holding your fingers in front of the 

opening.

2.  If you notice flue gas escaping, this indicates a dry condensate 

drain trap. See step 4 for procedure to fill trap. Call your qualified 

service technician to inspect the boiler and condensate line and 

refill the condensate trap if problem persists regularly.

Under some circumstances an SVF

TM

 vent system 

may not produce enough condensate to keep the 

condensate trap full of liquid. If the trap is not full, 

small amounts of flue products can be emitted into the 

boiler room through the condensate drain line. Follow 

procedure below to fill trap.

3.  Verify that the condensate drain line is unobstructed by slowly 

pouring water into the exhaust sampling port on near the flue 

connection (piping end of the boiler). The water should run out 

the end of the condensate drain line. If the water does not run 

out, call your qualified service technician to inspect the boiler 

and clean or replace the condensate drain line.

4.  Fill the condensate trap with fresh water, either by removing, filling 

and re-installing or by pouring water into the exhaust sampling 

port the flue connection (piping end of boiler).

5.  Loosen any attachments to the supplied flexible drain hose.

a.  Loosen the condensate trap inlet connection.

b.  Remove condensate trap and flush as needed.

The condensate trap must be filled with water during 

all times of boiler operation to avoid flue gas emission 

from the condensate drain line. Failure to fill the trap 

could result in severe personal injury or death.

Check automatic air vents

1.  See illustration at right.
2.  Remove the cap from any automatic air 

vent in the system and check operation 

by depressing valve “B” slightly with the 

tip of a screwdriver.

3.  If the air vent valve appears to be working 

freely and not leaking, replace cap “A”, 

twisting all the way on.

4.  Loosen cap “A” one turn to allow vent to 

operate.

5.  Have vent replaced if it does not operate 

correctly.

Figure 10

 

Automatic air vent located on right side of heat 

exchanger

Summary of Contents for SVF 1500-3000 Series

Page 1: ...y other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any telephone in your building Immediately call your gas supplier from a n...

Page 2: ...and use of the control display 5 8 Prevent air contamination Read the list of air contaminants you must avoid If found either remove the products permanently or have your installer relocate boiler ve...

Page 3: ...e to boiler personnel and or property may result Continual fresh makeup water will reduce boiler life Mineral build up in boiler heat exchanger reduces heat transfer over heats the metal and causes he...

Page 4: ...er See next page for location of interior boiler manual gas valve External manual gas valve Union Drip leg From gas supply Boiler gas connection Internal manual gas valve SVF Series 1 Commercial Conde...

Page 5: ...iler ON OFF switch Boiler gas connection Screen display use to monitor boiler operation change heating system setpoints and enable disable burner Boiler gas connection Boiler gas connection Screen dis...

Page 6: ...SVF Series 1 Commercial Condensing Gas Fired Water Boiler User s Information Manual 6 Part number 550 100 251 0819 The Control display Figure 4 SVF TM boiler s control display...

Page 7: ...month date year hour and minutes 2 Keeping the date and time current makes sure the control can record problems ac curately Figure 7 SVF TM boiler control display Maintenance notice screens BOILER STA...

Page 8: ...eset boiler as shown below To reset Press the DOWN or RIGHT arrow The display will go to the STATUS screen SETTINGS will be highlighted Press the DOWN arrow to move down to MANUAL RESET Press ENTER ce...

Page 9: ...nto the building Pleasereadtheinformationlistedbelow Ifcontaminatingchemicalswillbepresentnearthelocationoftheboiler combustionairinlet haveyourinstallerpipetheboilercombustionairandventtoanotherlocat...

Page 10: ...ure gauge Verify boiler front door is securely closed MONTHLY Check vent piping Check air piping Check relief valve Check condensate drain system Check automatic air vent PERIODICALLY Test low water c...

Page 11: ...ed and started annually at the beginning of the heating season by a qualified service technician In addition the maintenance and care of the boiler listed on Figure 9 page 10 and explainedinthismanual...

Page 12: ...iately or the boiler combustion air and vent termination must be relocated to another area Check the pressure temperature gauge 1 Make sure the pressure reading on the boiler pressure tempera turegaug...

Page 13: ...line and refill the condensate trap if problem persists regularly Under some circumstances an SVFTM vent system may not produce enough condensate to keep the condensate trap full of liquid If the tra...

Page 14: ...red indicat ing a low water condition 4 The SVF TM boiler s control will shut down the boiler on manual reset 5 The control display will flash red as shown in Figure 8 page 8 6 Select MANUAL RESET to...

Page 15: ...charge pipe to ensure that the valve does not weep after the line has had time to drain If the valve weeps lift the seat again to attempt to clean the valve seat If the valve continues to weep afterwa...

Page 16: ...SVF Series 1 Commercial Condensing Gas Fired Water Boiler User s Information Manual...

Reviews: