Weil-McLain New Series 3 Installation, Start-Up, And Operating Instructions Manual Download Page 27

®

Series 3 

WATER

 

BOILER

 — Boiler Manual

Check all piping for leaks

 

Eliminate all system or boiler leaks. Con-
tinual fresh make-up water will reduce 
boiler life. Minerals can build up in sec-
tions, reducing heat transfer, overheat-
ing heat exchanger, and causing heat 
exchanger failure. Leaking water may also 
cause severe property damage.

1.  Inspect all water and oil piping and verify to be leak 

free.

2.  Look for signs of leaking lines and correct any prob-

lems found.

3.  Check fuel lines and fuel unit as recommended in 

fuel unit  and burner manuals.

Check air openings

1.  Verify that combustion and ventilation air open-

ings to the boiler room and/or building are open 
and unobstructed. Check operation and wiring of 
automatic combustion air dampers, if used.

2.  Verify that boiler vent discharge and air intake are 

clean and free of obstructions.

Flue vent system and air piping

Visually inspect entire fl ue gas venting system (and 
air piping, if installed) for blockage, deterioration or 
leakage. Repair any joints that show signs of leakage 
in accordance with vent manufacturer’s instructions. 
When air is ducted to burner, verify that air inlet piping 
is connected and properly sealed.

 

Failure to inspect for the above condi-
tions and have them repaired can result 
in severe personal injury or death.

Check water system

1.  Verify all system components are correctly installed 

and operational.

2.  Check the cold fi ll pressure for the system. Verify it 

is correct (usually around 12 psig).

3.  Watch the system pressure as the boiler heats up 

(during testing) to ensure pressure doesn’t rise too 
high. Excessive pressure rise indicates expansion 
tank sizing or performance problem.

4.  Inspect automatic air vents and air separators. 

Remove air vent caps and briefl y press push valve 
to fl ush vent. Replace caps. Make sure vents do not 
leak. Replace any leaking vents.

Check expansion tank

General guidelines

Expansion tanks provide space for water to move in and 
out as the heating system water expands due to tempera-
ture increase or contracts as the water cools. Tanks may 
be open, closed or diaphragm or bladder type. Follow 
guidelines in this manual for the best location of the 
expansion tank.

 

Open-type

 — located above highest radiator or 

baseboard unit, usually in the attic or closet. Has a 
gauge glass and overfl ow pipe to a drain.

 

Closed-type

 — welded gas tight and located above 

boiler. Tank is partially fi lled with water, leaving an 
air cushion for expansion.

•  Make sure this type of tank is fi tted with a tank fi tting, 

such as the B & G Tank-Trol or Taco Taco-Trol. This 
fi tting reduces gravity circulation of air-saturated tank 
water back to the system and prevents the air from 
bubbling up through the water as it returns from the 
system.

•  Do not use automatic air vents in systems with closed-

type tanks. The air will escape from the system instead 
of returning to the tank. Eventually, the tank will 
waterlog and no longer control pressurization. The 
boiler relief valve will weep frequently.

 

Diaphragm or bladder-type

 — welded gas tight 

with a rubber membrane to separate the tank pres-
surizing air and the water. May be located at any 
point in the system, but most often found near the 
boiler.

•  Systems with this type of expansion tank require at least 

one automatic air vent, preferably located on top of an 
air eliminator, as shown in the example on page 15.

Troubleshooting a weeping relief valve

If relief valve has tended to weep frequently, the expan-
sion tank may be waterlogged or undersized.

 

Closed-type tank

 — tank is most likely water-

logged. Install a tank fi tting if not already installed. 
Then check fill level per fitting manufacturer’s 
instructions. If fi ll level is correct, check tank size 
against manufacturer’s instructions. Replace with 
a larger tank if necessary.

 

Diaphragm or bladder-type

 — fi rst, check tank 

size to be sure it is large enough for the system. If 
size is too small, add additional tank(s) as neces-
sary to provide suffi cient expansion. If tank size is 
large enough, remove tank from system and check 
charge pressure (usually 12 psig for residential ap-
plications). If tank won’t hold pressure, membrane 
has been damaged. Replace tank.

Annual service and start-up

 

(continued)

Part number 550-142-182/1014

27

Summary of Contents for New Series 3

Page 1: ...all instructions includ ing this manual and all other information shipped with the boiler before installing Perform steps in the order given Failure to comply could result in severe personal injury d...

Page 2: ...osen the center mounting bolt and rotate so the sight glass is in the 6 00 position 17 Over re pressure tapping 1 8 npt with plug 18 Jacket cross tie 19 Sensor wells Boiler limit temperature sensor an...

Page 3: ...Series 3 WATER BOILER Boiler Manual THE WATER BOILER Part number 550 142 182 1014 3...

Page 4: ...boiler Please have the boiler model number from the boiler rating label and the CP number from the boiler jacket You may list the CP number in the space provided on the Instal lation Certi cate found...

Page 5: ...boilerheatexchanger can be damaged by build up or corrosion due to sedi ment Do not use petroleum based cleaning or sealing compounds in boiler system Gaskets and seals in the system may be damaged Th...

Page 6: ...fied service technician to perform annual service Every day during heating season Keep area free of combustible materials Check that boiler area is free of combustible materials gasoline and other amm...

Page 7: ...e combustion air and ventilation Unless burner uses ducted outside air for combustion the boiler room must provide combustion air openings See manual page Venting Chimney venting Ensure the vent pipe...

Page 8: ...iler jacket surfaces Top of Control Pod cover 12 inches Sides and back 2 inches 5 Burner cover All directions 2 inches Combustible clearances always take pre cedence over service clearances For servic...

Page 9: ...dryer and replace Air from outside the building When outside air is used connect each opening directly or by ducts to the outdoors or to crawl or at tic space that freely connects with outdoors Size p...

Page 10: ...oiler leg Place the channel directly over the crate base runner as shown 5 Figure 3 With the boiler resting securely on the two 2 shipping channels screw a leveling leg in each boiler leg hole Screw l...

Page 11: ...temporarily The burner door is heavy Handle carefully to avoid potential for personal injury Do not damage the burner door insulation when han dling 5 The hinge bracket has keyhole slots Loosen the tw...

Page 12: ...ation in chimney Table 2 Chimney venting vent sizing Install the burner 1 Secure the burner ange to the burner door using the three 3 bolts provided 2 Check for secure placement of insulation and seal...

Page 13: ...d breeching draft will be approximately 0 01 to 0 02 W C Install barometric control in breech ing per control manufacturer s instructions when excess draft needs to be relieved or to comply with appli...

Page 14: ...for manufac turer s instructions Relief valve discharge piping To avoid water damage or scalding due to relief valve operation Discharge line must be connected to relief valve outlet and run to a safe...

Page 15: ...valve and makeup water added through ll valve Eventual section failure can result CLOSED expansion tank Figure 7 Ensure expansion tank size will handle boiler and system water volume and temperature...

Page 16: ...all zones Figure 8 Multiple zoning with circulators Temperatures 140 F and higher Figure 9 Multiple zoning with zone valves Temperatures 140 F and higher d Separate relay is required for each circula...

Page 17: ...to distribute heat to all zones b Separate transformer is required to power zone valves Refer to Weil McLain Zone Valve Wiring Guide for details 6 To set the valves 7a and 7b a Set the valves while th...

Page 18: ...l Code ANSI NFPA 70 latest edition and any additional national state or local codes Canada CSA C22 1 Canadian Electrical Code Part 1 and any local codes Figure 13 Terminal strip access Connect wiring...

Page 19: ...t installed or wired Wire the circulator to the boiler terminal strip as shown on the boiler wiring diagram Provide hot neutral and ground wires routed in metal conduit Thermostat wiring Install therm...

Page 20: ...iler Manual Connect wiring continued Figure 15 Boiler and burner wiring standard equipment This wiring diagram is for standard boiler equipment For wiring with optional AFM see AFM instructions Part n...

Page 21: ...Series 3 WATER BOILER Boiler Manual Connect wiring continued Part number 550 142 182 1014 21...

Page 22: ...device must be used to prevent ow of oil in case of oil line break Support oil lines as required by codes Make tank connections with swing joints or copper tubing to prevent breaking in case the tank...

Page 23: ...ombustion test equip ment to assure proper operation Do not re boiler without water Sections will overheat damaging boiler and resulting in substantial property damage 5 Vent air from system Repeat st...

Page 24: ...ly Refer to Thermostat wiring page 19 12 Boiler cycled with thermostat Raise to highest setting and verify boiler goes through normal start up cycle Lower to lowest setting and verify boiler goes off...

Page 25: ...oil burner motor if required clean air inlet clean or change fuel filter and strainer 8 Make sure boiler is filled with water 9 Start unit and verify combustion settings with combustion test equipment...

Page 26: ...NIOSH recommendations can be found on the NIOSH web site at http www cdc gov niosh homepage html NIOSH approved res pirators manufacturers and phone numbers are also listed on this web site Wear long...

Page 27: ...a ture increase or contracts as the water cools Tanks may be open closed or diaphragm or bladder type Follow guidelines in this manual for the best location of the expansion tank Open type located abo...

Page 28: ...ore operating lever check to see that a discharge line is connected to this valve directing the ow of hot water from the valve to a proper place of disposal Otherwise severe personal injury may result...

Page 29: ...the cleaning process 7 Remove the ue baf es 8 Starting at the top of the boiler use a wire ue brush to thoroughly clean all ns 9 Once the ueways are cleaned carefully remove the paper from the oor of...

Page 30: ...iring harness at the jacket cross tie located beneath the burner door Failure to disconnect the burner wiring har ness before opening the burner door can cause damage to the burner and boiler wiring T...

Page 31: ...ve the electrical tray in position 15 Remove the jacket side panels by pulling back edge away from the back of the boiler and then disengag ing the keyholes from the jacket front screws 16 Remove the...

Page 32: ...or well 592 300 026 9 Mounting clip for P T gauge and limit well 512 400 001 10 P T gauge pressure sensor check valve 512 400 000 11 Boiler relief valve 3 4 NPT 30 PSI 511 546 920 12 Flue collar 446 9...

Page 33: ...Series 3 WATER BOILER Boiler Manual Replacement parts continued Boiler section assembly parts Part number 550 142 182 1014 33...

Page 34: ...2 required 3 8 16 x 1 Purchase locally 5 Observation port assembly includes observation port bolt observation port gasket sight glass gasket sight glass water glass 386 902 000 6 Observation port gask...

Page 35: ...Series 3 WATER BOILER Boiler Manual Replacement parts continued Burner door parts Part number 550 142 182 1014 35...

Page 36: ...6 900 007 6 Jacket rear panel if required order insulation below 426 900 001 7 Jacket rear panel insulation 591 222 181 8 Jacket cross tie 426 900 009 9 Boiler insulation Not shown UO 3 UO 4 UO 5 591...

Page 37: ...Series 3 WATER BOILER Boiler Manual Replacement parts continued Jacket and control parts Part number 550 142 182 1014 37...

Page 38: ...ons 1 Boiler circulator is shipped loose Circulator may be mounted on either boiler supply or return piping 2 Relief valve is shipped loose supplied with elbow and nipple to install in rear section ta...

Page 39: ...y at combustion condition of 13 0 CO2 and 0 02 w c breeching draft 2 Ratings shown are for sea level applications only For altitudes above 2 000 feet derate the product capacity by 4 per 1 000 feet ab...

Page 40: ...40 Series 3 WATER BOILER Boiler Manual 40...

Reviews: