Figure 13
Typical piping (one riser shown on boiler)
Connect steam piping
(continued)
Boiler
Model
I=B=R gross
output lbs
steam per hour
Gallons
condensate
per hour
Minimum condensate receiver capacity – gal.
Recommended
condensate feed
pumping rate gpm at
15 psi
15 Min.*
Boiler
operation
30 Min.*
Boiler
operation
45 Min.*
Boiler
operation
60 Min.*
Boiler
operation
SGO-3
114
14
4
8
12
16
0.5
SGO-4
150
18
5
11
16
22
0.6
SGO-5
180
22
6
13
19
26
0.7
SGO-6
216
26
8
16
23
31
0.9
SGO-7
246
30
9
18
27
35
1.0
SGO-8
274
33
10
20
30
39
1.1
SGO-9
303
36
11
22
33
44
1.2
* Maximum time to when condensate returns to boiler.
Table 5
Condensate receiver capacity
Optional reservoir piping
Modern steam boilers are designed to steam for less
time than older, larger boilers. When replacing an older
steam boiler, the system condensate return time may
be longer than the steaming time. This can cause the
following problems:
•
Boilers fitted with an automatic water feed could
overfill.
•
Units fitted with only a low water cutoff would
shut down and cycle while waiting for condensate
to return.
To size and install reservoir piping, see Figure 13 and Bulletin AE-8403
(available through your Weil-McLain distributor or sales office):
1. Pipe boiler as shown on page 18 through page 20.
2. Use 8" diameter reservoir pipe.
3. Locate centerline of reservoir pipe 1" below 26
7
/
8
" boiler waterline.
Part number 550-141-829/1211
21
GOLD
SGO
OIL-FIRED NATURAL DRAFT STEAM BOILER — SERIES 3 —
Boiler Manual
SERVICE TECHNICIAN ONLY — read and follow completely.