Part number 550-100-090/0809
123
gas
-
fired
water
boiler
—
Boiler Manual
MAINTENANCE & SPECIFICA
TIONS
Ratings — multiple Ultra boilers
(continued)
Figure 127
Engineering data (see Figure 128 for notes)
Boiler
Model
Ultra –
Shipping
weight
Operating
weight
Water
content
Water flow rate
per boiler
Vent/air pipe
size —
Provide a
separate vent
for each boiler
Electrical
service
required
Pounds
per boiler
Pounds
per boiler
Gallons
per boiler
GPM
@ 20°F rise
GPM
@ 40°F rise
Amps
per boiler
Note 4
Note 5
Note 6
80
199
139
0 7
7 1
3 6
2” or 3”
15 0
105
207
145
0 8
9 4
4 7
2” or 3”
15 0
155
234
181
1 2
13 9
7 0
3”
15 0
230
246
192
1 6
20 7
10 4
3” or 4”
15 0
299
297
229
2 1
27 9
14 0
4”
15 0
399
297
229
2 1
36 5
18 2
4”
15 0
Figure 128
Notes for Figure 126 and Figure 127-
1
Based on standard test procedures outlined by DOE for individual boilers.
2
Net I=B=R ratings are based on piping and pickup allowance of 1.15.
Consult Weil-McLain Technical Services for other allowances.
3
Foundation sizes in Figure 126 provide 6 inches between boilers and 2 inches from boiler to edge of foundation.
Smaller foundations are possible with reduced service clearances.
See page 54 for details.
For side-to-side installations, see
•
Figure 56, page 54.
For back-to-back installations, see
•
Figure 57, page 54.
4
Operating weight is the total weight of the boiler, including water.
5
Ultra-80 and -105 vent/air pipes can be either 2” or 3” pipe. Vent/air pipe length limits for 2” piping are not as long as for 3” piping.
Ultra-230 vent/air pipes can be either 3” or 4” pipe. Vent/air pipe length limits for 3” piping are not as long as for 4” piping.
All Ultra installations require a separate vent pipe and termination for each boiler.
Vent piping cannot be manifolded
. Install and
terminate vents as described in vent/air installation instructions in this manual.
Combustion air piping can be individually piped or manifolded. See Figure 59, page 55, for manifolded air piping.
6
Total amp requirement includes up to three circulators, not exceeding 2.2 amps per circulator.