4
Analogueoutputtypeandrange
The output type (current/voltage) is like the input type as it is set by
manufacturing. The output range parameters let the PTX800A show
the output range correctly during review mode and prompt for the
correct values during calibration. They have no affect on the operation
of the instrument. If you change them you must be prepared to
calibrate the outputs.
OutputAction
Direct action results in the normal, proportional output. Reverse action
gives an output that is inverted with respect to the rate, so a rate of
zero gives a full scale output and vice versa.
DisplayIntensity
There are fourteen different levels.
•SetupSequence
Setting
Display
Description
Å
ì
PGM
S/W Version
vEr_1.01
S/W Version 1.01
-
-
Next
Inputs
Input type
InP=Cur
InP=voLt
Current (mA) based signal
Voltage based (V) based signal
Toggle
Accept
Input range
low value
InpLO=
4.00
Introduces Input low value
Value, e.g., 4.00 mA
-
Dec
-
Inc
Next
Accept
Input range
High value
InpHI=
20.00
Introduces Input high value
Value, e.g., 20.00 mA
-
Dec
-
Inc
Next
Accept
Input Calibra-
tion?
CALInY
CALInn
Calibrate the inputs
Skip Input calibration
Toggle
Accept
Damping
Factor
dFaCtor=
2
Introduces Input damping factor
Damping Factor , e.g., 2
-
Dec
-
Inc
Next
Accept
Transfer
Function
L nEAr
SQrroot
Linear
Square root
Toggle
Accept