InternalAdjustments(Inputbalancing)
This control allows for component
tolerances that would otherwise give
unequal outputs with both inputs at 4 mA
and with both inputs at 0 mA.
1. Remove the electronics from the case
and connect up as shown above.
. Set up two multimeters to measure the
voltages across terminals 4 & and
terminals 4 & .
. With both milliamp sources at 4.00 mA,
adjust the VR1 on the personality card
until both voltages are equal.
4. Repeat the adjustment with both milliamp sources at 0.00 mA.
. Repeat & 4 until no further improvements can be made.
3
+
–
DPA/MAS
2
4
DC mA
source
+
–
B
DC mA
source
A
14
7
VR1
. . . . . . . .