•Modifications
Changingtheinputoroutputrange
To change ranges:
1. Remove the four screws holding
the front panel in place (marked
A & B in the diagram).
. Remove the front panel. Take care not to lose the plastic insulators
which fit over the potentiometer screws - they are essential to
maintain specified isolation.
. Select the switches according to the table below.
Input
Channelone(S1)
Channeltwo(S101)
Bit1 Bit2 Bit3 Bit4 Bit1 Bit2 Bit3 Bit4
4-20 mA
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
0-20 mA
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
0-10 V
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
±10 V
OFF
ON
ON
OFF
OFF
ON
ON
OFF
Output
Channelone(S2)
lK4
Channeltwo(S102)
lK5
Bit1 Bit2 Bit3 Bit4
Bit1
Bit2
Bit3
Bit4
4-20 mA
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
ON
OFF
0-10 V
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
0-5 V
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
4. Replace the front panel.
5. Calibrate the unit.