![Weidmüller DFI Operating Instructions Manual Download Page 11](http://html1.mh-extra.com/html/weidmuller/dfi/dfi_operating-instructions-manual_952255011.webp)
11
•Calibration
general
All instruments are fully calibrated before leaving the factory and
should not need adjustment until the next scheduled calibration.
There are two independent sets of controls marked CH1 (for channel
one) and CH (for channel two).
equipmentrequirements
• A suitable Current (mA) / Voltage (V) source
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)
• Flat bladed screwdriver (blade width less than .54 mm / 0.1 inch)
ZeROandSpANadjustment
The ZERo and SpAN controls are on the front panel of the transmitter.
Turn the control clockwise to increase the zero or span.
Note: ‘zero’ means the lowest point in the signal range, so for a
4-0 mA signal, ‘zero’ is 4 mA. ‘Full scale’ refers to the highest point in
the signal range.
1. Connect up the instrument, with the signal source as input and the
multimeter measuring the output.
. Set the input source to ‘zero’.
. Turn the ZERo adjustment until the output is at ‘zero’.
4. Set the input source to ‘full scale’.
5. Adjust the SpAN control until the output is at ‘full scale’.
6. Recheck the ZERo adjustment.
7. Recheck the SpAN adjustment.
Summary of Contents for DFI
Page 2: ... ...
Page 8: ... LK4 S2 S1 ...
Page 13: ...13 LK4 S2 S1 ...
Page 14: ...14 ...
Page 15: ...15 ...