Connecting the SAI Distributor
5663600000/1.4/09.09
81
5.12 SAI-AU M12 SB 4THERMO
The SAI distributor Active Universal is equipped with
the functions of a decentralised I/O system. Each
distributor is equipped with module-specific actua-
tor/sensor functions and a sub-bus interface. The
modules combine the complete electronics in a wa-
ter- and dust-proof protected housing. This enables
their use in harsh environments.
The module SAI-AU M12 SB 4THERMO is designed
to connect four thermocouples with four M12 con-
nectors.
Figure 52
SAI-AU M12 SB 4THERMO
HINWEIS
After a change of the Subbus modules is
in many situations a new start of the ga-
teway necessary.
LEDs
UB
Supply voltage UB
Supplies the module and the
Plug-in stations 1 to 4
Com
Communication with the
gateway
AI0 to AI3
Analogue inputs
Connections
SUB IN
Sub-bus input
SUB OUT
Sub-bus output
1 to 4
4 inputs
Table 61
SAI-AU M12 SB 4THERMO
Connection of supply voltage
The power supply is 24 V DC in accordance with EN
61131-2; the permissible range is 18 to 30 V DC.
The distributor is designed to offer protection against
polarity reversal.
Module connection from SUB-IN
Contact system
M8 male connector, 4-pole
Coding -
Pin assignment
Pin 1: + 24 Vdc
Pin 2: Data +
Pin 3: GND
Pin 4: Data -
Housing: Shield, connected
with the FE
Table 62
Contact assignment for the sub-bus
male connector
AI3
Thermo
U
B
COM
IN
OUT
BUS
AI2
AI1
AI0
Summary of Contents for SAI Active Universal Pro Series
Page 2: ......
Page 10: ...Notes on Safety 10 5663600000 1 4 09 09...
Page 11: ...SAI Pro 2 SAI Pro 2 1 Pro Description 12 2 2 PROFIBUS DP 14 5663600000 1 4 09 09 11...
Page 20: ...Project Planning with the Universal Pro 20 5663600000 1 4 09 09...
Page 28: ...Mounting SAIs 28 5663600000 1 4 09 09...
Page 95: ...Connecting the SAI Distributor 5663600000 1 4 09 09 95...
Page 177: ......