• InstrumentSetup
For setup mode, connect the security link and press
PGM
and
ENT
keys
simultaneously. The software version will be displayed. If you wish to
continue, press
ENT
within 10 s.
Setting
Display
Description
Å
ì
ENT
S/W Version
v1.01
S/W Version 1.01 (Note: this information only applies to versions
1.00 to 1.09)
DisplayandInputs
Display
Brightness
LOBr
HIBr
Low brightness
High brightness
Toggle
Accept
Input format
IP=1
IP=E
Current (mA)
Voltage (V)
Toggle
Accept
IPL=
4.00
Input range lower limit
e.g., 4.00 mA
-
Dec
-
Inc
Next
Accept
IPH=
20.00
Input range upper limit
e.g., 20.00 mA
-
Dec
-
Inc
Next
Accept
Damping factor
dF=
2
Introduces the damping factor
Value, e.g., 2
-
Dec
-
Inc
Next
Accept
Linearisation
LInr
Sr
Linear
Square root
Toggle
Accept
Display range
dP=
.
Decimal point position
-
Shift
Next
Accept
dLO=
0.0
Display range lower limit
e.g., 0.0
-
Dec
-
Inc
Next
Accept
dHI=
100.0
Display range Upper limit
e.g., 100.0
-
Dec
-
Inc
Next
Accept
Analogueoutputs*
Analogue output
select
AOPY
AOPN
Enabled
Disabled (Select this option for PMX420)
Toggle
Accept
Analogue output
range
OPL=
4.00
Output low value
e.g., 4.00
-
Dec
-
Inc
Next
Accept
OPH=
20.00
Output high value
e.g., 20.00
-
Dec
-
Inc
Next
Accept
Note: if you change the output range you must calibrate the outputs.
Output action
OP=d
OP=r
Direct
Reversed
Toggle
Accept
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]