Parameter
Description
Range of values
Decimal
places
Index
Net Id
Size
0 = Inactive
1 = Fault F081
2 = Alarm A081
C5.4.2.2
Level
0 to 99 %Pn
0
23C4h
964
8bit
C5.4.2.3
Time
1 to 99 s
0
23C5h
965
8bit
C5.5
Phase Sequence
C5.5.1
Mode
23A2h
930
enum
0 = Inactive
1 = RST - Fault F067
2 = RTS - Fault F068
C5.6
Bypass Protections
C5.6.1
Undercurrent
2397h
919
enum
0 = Inactive
1 = Fault F076
C5.6.2
Overcurrent
2398h
920
enum
0 = Inactive
1 = Fault F063
C5.6.3
Closed
2399h
921
enum
0 = Inactive
1 = Fault F077
C5.7
Time Protections
C5.7.1
Before Start
0.5 to 999.9 s
1
23A3h
931
16bit
C5.7.2
After Stop
2.0 to 999.9 s
1
23A4h
932
16bit
C5.7.3
Between Start
2 to 9999 s
0
23A5h
933
16bit
C5.8
Motor Thermal Protection
C5.8.1
Ch1 Installed Sensor
C5.8.1.1
Mode
23EEh
1006
enum
0 = Off
1 = On
2 = On Stator
C5.8.2
Ch1 Sensor Fault
C5.8.2.1
Mode
23E6h
998
enum
0 = Fault F109 and F117
1 = Alarm A109 and A117
C5.8.3
Ch1 Overtemperature
C5.8.3.1
Mode
23C6h
966
enum
0 = Fault F101
1 = Alarm A101
2 = F101 and A101
C5.8.3.2
Fault Level
0 to 250
◦
C
0
23C7h
967
8bit
C5.8.3.3
Alarm Level
0 to 250
◦
C
0
23C8h
968
8bit
C5.8.3.4
Alarm Reset
0 to 250
◦
C
0
23C9h
969
8bit
C5.8.4
Ch2 Installed Sensor
C5.8.4.1
Mode
23EFh
1007
enum
0 = Off
1 = On
2 = On Stator
SSW900
|
58