SSW7000 | 5-30
5.2.10.
User Signal and Control Connections
The signal connections (analog inputs and outputs) and control (digital inputs and outputs) available to the user
are performed in the control board 1 (CC11).
Figure 5.34: XC1 terminal strip description
Terminal Strip
Factory Setting Function
Specifications
1
+REF
Potentiometer positive referente
Output v5.4 V, ±5 %.
Maximum output current: 2 mA
2
AI1+
Analog Input 1:
No function
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
IN
= 400kΩ)
Signal: 0 to 20mA or 4toa 20mA (R
IN
= 500Ω)
Maximum voltage: ±30 V
3
AI1-
4
REF
Potentiometer negative reference
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
5
AI2+
Analog Input 2:
No function
Differential
Resolution: 11 bits + signal
Signal: 0 to 10 V (R
IN
= 400kΩ)
Signal: 0 to 20mA or 4 to 20mA (R
IN
= 500Ω)
Maximum voltage: ±30 V
6
AI2-
7
AO1
Analog output 1:
No function
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥10kΩ)
Signal: 0 to 20mA or 4 to 20mA (R
L
≤ 500Ω)
Protected against short circuit
8
AGND (24 V)
Reference (0 V) for analog ouputs Connected to the ground (frame) throught impedance:
940 Ω resistor in parallel with a 22 nF capacitor
9
AO2
Analog output 2:
No function
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
≥10kΩ)
Signal: 0 to 20mA or 4 to 20mA (R
L
≤ 500Ω)
Protected against short circuit
10
AGND (24 V)
Reference (0 V) for the analog
outputs
Connected to the ground (frame) throught impedance:
940 Ω resistor in parallel with a 22 nF capacitor
11
DGND*
Reference (0 V) for the 24 Vdc
power supply
Connected to the ground (frame) throught impedance:
940 Ω resistor in parallel with a 22 nF capacitor
12
COM
Common point of the digital
Inputs
13
24 Vcc
24 Vdc power supply
24 Vdc, ±8 % power supply
Capacitor: 500 mA
14
COM
Common point of the digital
Inputs
15
DI1
Digital Input 1:
Start / Stop
6 Isolated digital Inputs
High level ≥ 18 V
Low level ≤ 3 V
Maximum input voltage. = 30 V
Input current: 11 mA @ 24 Vcc
16
DI2
Digital Input 2:
Reset
17
DI3
Digital Input 3:
No function
18
DI4
Digital Input 4:
No function
19
DI5
Digital Input 5:
No function
20
DI6
Digital Input 6:
No function
21
NF1
Digital output 1 DO1
Running
Contact rating:
Maximum voltage: 240 Vcac
Maximum current: 1 A
NF – Normally closed contact
C - Common
NA – Normally open contact
22
C1
23
NA1
24
NF2
Digital output 2 DO2
Bypass
25
C2
26
NA2
27
NF3
Digital output 3 DO3
Fault
28
C3
29
NA3