C CONFIGURATION
5 C CONFIGURATION
Allows accessing starter manager SCW100 writing variables.
C2 COMMUNICATION
Write parameters that allow configure the communication interfaces for the product.
C2 Communication
P0101: Action for Communication Fault
Range:
0 ... 1
Default:
1
Description:
It allows configuring the protection tripping mode for communication error.
Indication
Description
0 = No Action
No tripping.
1 = Disable Outputs
Turns off all product outputs. It is equivalent to receiving the stop command for the
starts, and clearing the command word for the digital outputs.
C2 Communication
P0032: CAN - Bus Off Reset
Range:
0 ... 1
Default:
0
Description:
It allows programming the inverter behavior when detecting a bus off error at the CAN interface.
Indication
Description
0 = Manual
If bus off occurs, LED will indicate this condition and the communication will be disabled.
The action programmed in parameter P0101 - Action for Communication Fault will be
performed. In order that the device communicates again through the CAN interface, it
will be necessary to power cycle the device.
1 = Automatic
If bus off occurs, the communication will be reinitiated automatically and the error will be
ignored. In this case it will not indicate this error at LEDs and the device will not perform
any error action.
SCW100 | 15