5
DETAILED PARAMETER DESCRIPTION
AI2 has a variation range from -10 V to 10 V no matter if P0239 = 0 or 4, that is, an input voltage of 0 V
corresponds in P0019 = 50 %. If it is necessary that 0 V correspond to P0019 = 0 %, the following setting
must be done:
GAIN
P0238
P0248
AI2' - P0019
AI2'
Reading
+
+
AI2
P0239
OFFSET (P0240)
Figure 5.30:
Block diagram of analog input AI2
P0239 - AI2 Signal Type
Adjustable range:
0 to 4
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
When current signals are used at AI2 input, put S2.B on the MVC4 control card in “ON” position.
For options 2 and 3 inverse reference is attained, that is, maximum speed is obtained with minimum reference.
Table 5.39:
AI2 Signal Type
Function
0
(0 to 10) V/(0 to 20) mA
1
(4 to 20) mA
2
(10 to 0) V/(20 to 0) mA
3
(20 to 4) mA
4
(-10 to +10) V
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0240 - Analog input AI2 offset (bipolar MVC4 board)
Adjustable range:
-100.0 to 100.0 %
Factory setting:
0.0 %
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
Description:
Refer to P0238.
P0241 - AI3 signal function
Adjustable range:
0 to 3
Factory setting:
0
Acesso:
Menu
→
Configurations
→
I/O
→
Analog inputs
MVW3000 | 5-47