Commissioning
NOTE!
The frequency inverter uses the 3
rd
Ramp to decelerate the motor when the
SS1-t safety function is requested. The frequency inverter uses the 3
rd
Ramp
to decelerate the motor when the SS1-t safety function is requested. Therefore,
when using SS1-t, only modify this parameter during the configuration of the
CFW500-SFY2.
P0108 - SS1-t Time
Adjustable
Range:
0 to 999 s
Factory
Setting:
0 s
Properties:
sy
Access Groups
via HMI:
Description:
It defines the delay time of the SS1-t safety function to be programmed in the safety functions
module. If the delay time value is 0 seconds, the safety functions module is programmed with
the STO safety function.
NOTE!
P0108 is only visible on HMI and, therefore, can only be modified when the
safety functions module is in the programming mode.
P0109 - SS1-t Time Confirmation
Adjustable
Range:
0 to 999 s
Factory
Setting:
Properties:
ro, sy
Access Groups
via HMI:
Description:
During the programming procedure of the safety functions module, it indicates the actual value
of the delay time programmed in the safety module for the user's confirmation.
NOTE!
P0109 is only visible on HMI and, therefore, can only be accessed when the
safety functions module is in the programming mode.
Summary of Contents for CFW500 Series
Page 2: ...Safety Manual Series CFW500 Language English Document 10006503387 01 Date 10 2019 ...
Page 5: ...4 CFW500 English Contents ...
Page 10: ...CFW500 9 English Safety 1 4 DECLARATION AND CERTIFICATION ...
Page 28: ...Manual de Seguridad Série CFW500 Idioma Español Documento 10006503387 01 Fecha 10 2019 ...
Page 31: ...30 CFW500 Español Sumario ...
Page 36: ...CFW500 35 Español Seguridad 1 4 DECLARATION Y CERTIFICACION ...
Page 57: ...56 CFW500 Português Sumário das Revisões ...
Page 62: ...CFW500 61 Português Segurança 1 4 DECLARAÇÃO E CERTIFICAÇÂO ...