V/f Scalar Control
9-4 | CFW300
9
P136 - Manual Torque Boost
Adjustable
Range:
0.0 to 30.0 %
Factory
Setting:
5.0 %
Properties:
V/f
Description:
It actuates at low speeds, that is, in the range 0 to P146 (V/f) or 0 to P145 (Quadratic V/f), increasing the inverter
output voltage so as to compensate the voltage drop in the motor stator resistance in order to keep the torque
constant.
The optimum setting is the smallest value of P136 which allows the motor satisfactory start. A value greater
than necessary will excessively increase the motor current at low speeds, which may lead the inverter to a fault
condition (F051 or F070) or alarm condition (A046 or A050), as well as motor overheating.
and
show the actuation regions of the Torque Boost for the V/f and Quadratic
V/f mode, respectively.
P134
P145
P146
P
0
P
1
P
2
P
3
P142
P143
P136
Output
frequency (Hz)
Output
voltage (%)
Figure 9.4:
Torque boost region for V/f control mode
P134
P145
P142
P136
Output
frequency (Hz)
Output
voltage (%)
Figure 9.5:
Torque boost region for quadratic V/f control mode
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...