Logical Command and Speed Reference
7-12 | CFW300
7
P680 - Logical Status
Adjustable
Range:
0 to FFFF (hexa)
Factory
Setting:
-
Properties:
ro
Description:
The inverter status word is unique for all the sources and can only be accessed for reading. It indicates all the
relevant operating status and modes of the inverter. The function of each bit of P680 is described in
Table 7.4:
Status word
BIT
Function
Description
0
Reserved
-
1
Run Command
0:
There was no Run command
1:
There was Run command
2
Fire Mode
0:
Fire Mode function inactive
1:
Fire Mode function active
3 and 4 Reserved
-
5
2
nd
Ramp
0:
1
st
acceleration and deceleration ramp by P100 and P101
1:
2
nd
acceleration and deceleration ramp by P102 and P103
6
Config. Status
0:
inverter operating in normal conditions
1:
inverter in configuration state. It indicates a special condition in which the inverter cannot be
enabled, because it has parameterization incompatibility
7
Alarm
0:
inverter is not in alarm state
1:
inverter is in alarm state
8
Running
0:
motor is stopped
1:
inverter is running according to reference and command
9
Enabled
0:
inverter is completely disabled
1:
inverter is completely enabled and ready to turn the motor
10
Forward
0:
motor is running in the reverser direction
1:
motor is running in the foward direction
11
JOG
0:
JOG function inactive
1:
JOG function active
12
Remote
0:
inverter in Local mode
1:
inverter in Remote mode
13
Undervoltage
0:
no undervoltage
1:
with undervoltage
14
Reserved
-
15
Fault
0:
inverter is not in fault state
1:
some fault registered by the inverter
P682 - Serial / USB Control
P684 - CANopen / DeviceNet / Profibus DP Control
Adjustable
Range:
0000h to FFFFh (hexa)
Factory
Setting:
-
Properties:
ro
Description:
The inverter control word for a certain source is accessible for reading and writing, but read only access is
permitted for the other sources. The inverter has a common word for each interface, which is defined by the
function of its bits separately as per
. The value of P682 is indicated in hexadecimal.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...