SoftPLC
18-8 | CFW300
18
P910 – PID Controller Application Version
Faixa de
Valores:
0.00 to 90.00
Factory
Setting:
-
Propriedades:
ro
Description:
Read-only parameter which presents the software version of the PID controller application developed for the
SoftPLC function of the CFW300.
P911 – Control Setpoint
Adjustable
Range:
-99.99 a 99.99 [Eng. Un. SoftPLC]
Factory
Setting:
2.00
Properties:
rw
Description:
This parameter defines the setpoint value in automatic mode for the PID controller in engineering unit when the
control setpoint source is programmed to be via HMI or communication networks (P920=0). When the control
setpoint source is programmed for some other source (P920≠0), this parameter will show the present setpoint
in automatic mode for the PID controller.
NOTE!
This parameter will be viewed according to the selection of the parameters for the SoftPLC engineering
unit (P510 and P511).
P912 – Control Setpoint 1
P913 – Control Setpoint 2
P914 – Control Setpoint 3
P915 – Control Setpoint 4
Adjustable
Range:
-99.99 a 99.99 [SoftPLC Eng. Un.]
Factory
Setting:
P912 = 2.00
P913 = 2.30
P914 = 1.80
P915 = 1.60
Properties:
Description:
These parameters define the setpoint value in automatic mode of the PID controller in engineering unit
when the control setpoint source is programmed to be via logical combination of digital inputs DI3 and DI4
(P950 = 4, 5 or 6) according to
.
Table 18.4:
Truth table for the control setpoint via logical combination of digital inputs DI3 and DI4
P912 – Control
Setpoint 1
P913 – Control
Setpoint 2
P914 – Control
Setpoint 3
P915 – Control
Setpoint 4
Digital input DI3
0
1
0
1
Digital input DI4
0
0
1
1
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...