Digital and Analog Inputs and Outputs
12-22 | CFW300
12
Table 12.7:
Digital Output Functions
Value
Function
Description
0
Not used
It deactivates the digital output
1
F* ≥ Fx
Active when the frequency reference F* (P001) is greater or iqual the Fx (P281)
2
F ≥ Fx
Active when the Output Frequency F (P002) is greater or iqual the Fx (P281)
3
F ≤ Fx
Active when the Output Frequency F (P002) is smaller or iqual the Fx (P281)
4
F = F*
Active if the Output Frequency F (P002) is equal to the reference F* (P001) (ramp end)
5
Not used
It deactivates the digital output
6
Is > Ix
Active if the output current Is (P003) > Ix (P290)
7
Is < Ix
Active if the output current Is (P003) < Ix (P290)
8
Torque > Tx
Active if the motor torque T (P009) > Tx (P293)
9
Torque < Tx
Active if the motor torque T (P009) < Tx (P293)
10
Remote
Active if the command is in the remote situation (REM)
11
Run
Active if the motor is running (active output PWM pulses)
12
Ready
Active if the inverter is ready for enabling
13
Without fault
Active if the inverter has no faults
14
Without F070
Active if the inverter has no overcurrent fault (F070)
15
Not used
It deactivates the digital output
16
Without F021/F022
Active if the inverter has no overvoltage or undervoltage fault (F022 or F021)
17
Not used
It deactivates the digital output
18
Without F072
Active if the inverter has no motor overload fault (F072)
19
4-20 mA OK
Active if AIx setting is 4 to 20 mA (P233 = 1 or 3) and AIx < 2 mA
20
Value of P695
Status of the bits 0 to 4 of P695 activate digital outputs DO1 to DO5, respectively
21
Forward
Active if the inverter direction of rotation is forward
22 to 23
Not used
It deactivates the digital output
24
Ride-Through
Active if the inverter is executing the Ride-Through function
25
Pre-Charge OK
Active if the pre-charge relay of the DC link capacitors was already activated
26
With fault
Active if the inverter has a fault
27
Not used
It deactivates the digital output
28
SoftPLC
It activates the output DOx according to the SoftPLC memory area. Check the SoftPLC user
manual
29 to 34
Not used
It deactivates the digital output
35
Without alarm
Active when the inverter has no alarms
36
Without fault and alarm Active when the inverter has neither alarms nor faults
37
Application Function 1
If activates the output DOx according to the application of SoftPLC
38
Application Function 2
If activates the output DOx according to the application of SoftPLC
39
Application Function 3
If activates the output DOx according to the application of SoftPLC
40
Application Function 4
If activates the output DOx according to the application of SoftPLC
41
Application Function 5
If activates the output DOx according to the application of SoftPLC
42
Application Function 6
If activates the output DOx according to the application of SoftPLC
43
Application Function 7
If activates the output DOx according to the application of SoftPLC
44
Application Function 8
If activates the output DOx according to the application of SoftPLC
45
Fire Mode
Activates DOx output when Fire Mode is enabled
46
Process Control
Process Variable Low Level (A760/F761) (For P903 = 1)
(*)
47
Process Control
Process Variable High Level (A762/F763) (For P903 = 1)
(*)
(*)
For further details refer the
Chapter 18 APPLICATIONS on page 18-1
.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...