Digital and Analog Inputs and Outputs
CFW300 | 12-13
12
Table 12.6:
Digital input functions
Value
Description
Dependence
0
Not used
-
1
Run/Stop command
P224 = 1 or P227 = 1
2
General Enable command
-
3
Fast Stop
P224 = 1 or P227 = 1
4
Forward run command
(P224 = 1 and P223 = 4) or
(P227 = 1 and P226 = 4)
5
Reverse run command
P224 = 1 or P227 = 1
6
Start command
P224 = 1 or P227 = 1
7
Stop command
P224 = 1 or P227 = 1
8
Forward Rotation Direction
P223 = 4 or P226 = 4
9
Local/Remote selection
P220 = 4
10
JOG command
(P224 =1 and P225 = 2) or
(P227 =1 and P228 = 2)
11
Electronic Potentiometer: Accelerate E.P.
P221 = 7 or P222 = 7
12
Electronic Potentiometer: Decelerate E.P.
P221 = 7 or P222 = 7
13
Multispeed reference
P221 = 8 or P222 = 8
14
2
nd
Ramp selection
P105 = 2
15 to 17
Not used
-
18
No external alarm
-
19
No external fault
-
20
Fault reset
Active fault
21 to 23
Not used
-
24
Disable flying start
P320 = 1 or 2
25
Not used
-
26
Lock Prog.
-
27 to 31
Not used
-
32
Multispeed reference with 2
nd
Ramp
(P221 = 8 or P222 = 8) and P105 = 2
33
Electronic Potentiometer: Accelerates E.P. with 2
nd
Ramp
(P221 = 7 or P222 = 7) and P105 = 2
34
Electronic Potentiometer: Decelerates E.P. with 2
nd
Ramp
(P221 = 7 or P222 = 7) and P105 = 2
35
Forward run with 2
nd
Ramp
(P224 = 1 and P223 = 4) or
(P227 = 1 and P226 = 4) and P105 = 2
36
Reverse run with 2
nd
Ramp
(P224 = 1 and P223 = 4) or
(P227 = 1 and P226 = 4) and P105 = 2
37
Accelerates E.P./Start
P224 = 1 or P227 = 1
P221 = 7 or P222 = 7
38
Decelerates E.P./ Stop
P224 = 1 or P227 = 1
P221 = 7 or P222 = 7
39
Stop command
P224 = 1 or P227 = 1
40
Safety switch command
P224 = 1 or P227 = 1
41
Application Function 1
-
42
Application Function 2
-
43
Application Function 3
-
44
Application Function 4
-
45
Application Function 5
-
46
Application Function 6
-
47
Application Function 7
-
48
Application Function 8
-
49
Activate Fire Mode
(*)
50
Manual/Automatic PID (Only DI2 for P903 = 1)
(*)
51
Increase Setpoint Command (PE) (Only DI3 for P903 = 1)
(*)
52
Decrease Setpoint Command (Only DI4 for P903 = 1)
(*)
53
1st DI Control Setpoint (Only DI3 for P903 = 1)
(*)
54
2st DI Control Setpoint (Only DI4 for P903 = 1)
(*)
(*)
For further details refer the
Chapter 18 APPLICATIONS on page 18-1
.
Summary of Contents for CFW300 V1.3X
Page 2: ......
Page 8: ...Contents...
Page 46: ...Identification of the Inverter Model and Accessories 6 4 CFW300 6...
Page 60: ...Logical Command and Speed Reference 7 14 CFW300 7...
Page 72: ...V f Scalar Control 9 10 CFW300 9...
Page 80: ...VVW Vector Control 10 8 CFW300 10...
Page 116: ...Digital and Analog Inputs and Outputs 12 24 CFW300 12...
Page 132: ...Reading Parameters 15 6 CFW300 15...