LX3V-2TC2DAI-BD 

User manual 

 

 

 

 

 

 

Website:

 

http://www.we-con.com.cn/en

   

Technical Support:

 

[email protected]

   

Skype:

 fcwkkj 

Phone:

 86-591-87868869  

QQ:

 1043098682 

Technical forum:

 

http://wecon.freeforums.net/

   

 

Summary of Contents for LX3V-2TC2DAI-BD

Page 1: ...LX3V 2TC2DAI BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...it of the LX3V can only use one BD board Don t try to use two or more BD boards these BD boards will not work 5 When mounting module to PLC all the lights are blinking after power ON PLC it means this...

Page 3: ...communicating PLC OFF when timeout CH1 LED LED for CH1 constantly ON when analog signal in range lit when analog signal out of range K type 100 1200 J type 100 600 M8112 OFF K type M8112 ON J type CH2...

Page 4: ...0 70mA Powered by PLC host Temperature input TC Analog input signal Thermocouple K or J type 2 channels CH1 CH2 Range of rated temperature K 100 1200 J 100 600 Digital output K 1000 12000 J 1000 6000...

Page 5: ...e cable shall be grounded But their grounding point can be the same with high voltage lines 3 Never connect cable with forbidden size 4 Fix the cable so that the stress does not act on the terminal bo...

Page 6: ...e cable stripped jacket Then connect the cable AWG16 1 309 5 2 Input and output mode 1 Thermocouple input mode 2 Current Output Mode 6 Example The analog values of each channel are transfer to digital...

Page 7: ...er counter 6 2 Application example Since the LX3V 2TC2DAI BD does not have offset and gain functions if it needs for the values out of the standard specifications Additional programming orders will be...

Page 8: ...mula Fahrenheit Celsius 9 5 32 the unit is 0 1 2 Current output mode In current output mode it changes the digital value 0 2000 to analog value 4 20mA If the real digital range is 0 A A means any valu...