background image

4

TYPICAL 20 LP PROPANE GAS SUPPLY INSTALLATION

We strongly recommend that you use the Summit

®

 Built-In Tank Cabinet 

(#21280) for installations using a 20 lb LP cylinder, mounted remotely in an 
“island” structure.
The Summit

®

 Built-In Tank Cabinet is a CSA listed accessory for installing a 

remote mounted 20 lb LP cylinder, in an “island” structure. Summit

®

 Built-In 

Tank Cabinet has a hose and regulator assembly and gas connections, 
for connecting a remote mounted LP cylinder to the Summit

®

 Built-In gas 

grill. The hose and regulator is listed as a required part of the CSA listed 
Summit

®

 Built-In gas grill.

The Summit

®

 Built-In Tank Cabinet also meets the requirements for venting, 

tank retention and separation of the LP cylinder from a heat source as 
outlined in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/
CSA 1.6 for LP enclosures.
The Summit

®

 Built-In Tank Cabinet has its own installation guide.

If you do not use the Summit

®

 Built-In Tank Cabinet, you need to hire 

a licensed contractor or licensed plumber and they need to follow the 
requirements described in the ANSI Standard for Outdoor Cooking Gas 
Appliances, Z21.58/CSA 1.6 for LP enclosures.
The requirements described in the Standard for Outdoor Cooking Gas 
Appliances, Z21.58/CSA 1.6. are as follows;
A remote enclosure for an LP gas cylinder shall be ventilated by openings at 
both the upper and lower levels of the cylinder. This shall be accomplished 
by one of the following:

a).  One side of the remote LP cylinder enclosure shall be completely 

open; or 

b).  If the remote LP cylinder enclosure is designed to have four sides, 

a top and a bottom, ventilation is required for the remote LP cylinder 
enclosure;

1).  There should be at least two ventilation openings, (a hole or 

group of holes, for the purpose of ventilation) in the sidewalls 
of the island structure. The openings should be located within 
5 inches (127mm) of the top of the enclosure. The ventilation 
openings should be equally sized and spaced at a minimum of 90 
degrees, and be unobstructed. The openings shall have a total 
free open area of not less than 20 square inches. (This relates to1 
square inch of ventilation area, per pound of stored fuel capacity).

2).  Ventilation openings (a hole or group of holes, for the purpose of 

ventilation) should be provided at fl oor level. The ventilation openings 
should have a total free area of not less than 10 square inches. (This 
relates to 1/2 square inch of ventilation area, per pound of stored 
fuel capacity). There should be at least two ventilation openings 
if the ventilation openings at fl oor level are in the sidewall. The 
ventilation openings should be within 5 inches (127mm) of the fl oor. 
The ventilation openings should be of equal size and be spaced at a 
minimum of 90 degrees, and should be unobstructed. 

3).  The minimum size of the ventilation hole (s) should not be less 

than 1/4 inch. 

4).  The ventilation openings in the sidewalls should not allow 

venting into the empty or “hollow” area of the “island”. If a 
gas leak should occur or the LP cylinder should vent in the 
LP cylinder enclosure, the gas should not be allowed to vent 
or migrate into the empty or “hollow” area of the “island”.  
Ventilation openings in the sidewalls of the enclosure should 
only communicate with the outside of the “island” structure, so 
that the gas can dissipate outside of the “island” structure. 

c).  If the remote LP cylinder enclosure has four sides, a top and a 

bottom, and is intended for installation in a built-in “island” enclosure;
1).  At least one ventilation opening (a hole or group of holes, 

for the purpose of ventilation) needs to be on one side of the 
enclosure that communicates with the outside of the “island” 
structure. If a gas leak should occur or the LP cylinder should 
vent in the LP cylinder enclosure, the gas should not be 
allowed to vent or migrate into the empty or “hollow” area of 
the “island”.  Ventilation openings should only communicate 
with the outside of the “island” structure, so that the gas can 
dissipate outside of the “island” structure. The ventilation 
opening should be located within 5 inches (127mm) of the top 
of the enclosure, and should have a total free area of 20 square 
inches. (This relates to 1 square inch of ventilation area, per 
pound of stored fuel).

2).  At least one ventilation opening (a hole or group of holes, for the 

purpose of ventilation) needs to be on one side of the enclosure 
that communicates with the outside of the “island” structure, at the 
bottom. If a gas leak should occur or the LP cylinder should vent in 
the LP cylinder enclosure, the gas should not be allowed to vent or 
migrate into the empty or “hollow” area of the “island”.  Ventilation 
openings should only communicate with the outside of the “island” 
structure, so that the gas can dissipate outside of the “island” 
structure. The ventilation opening should be located within 5 inches 
(127mm) of the bottom of the enclosure, and should have a total 
free area of 10 square inches. (This relates to 1/2 square inch of 
ventilation area, per pound of stored fuel).
3).  The minimum size of the ventilation hole (s) should not be less 

than 1/4 inch.

d).  The remote LP cylinder enclosure should be constructed with non-

combustible materials. The remote LP cylinder enclosure should 
isolate the LP cylinder from the burner compartment, so that it 
provides shielding from radiation, be a fl ame barrier and provide 
protection from foreign material such as hot drippings. 

e).  There should be a minimum of 2 inches (50.8mm) between the 

ground and the fl oor of the remote LP cylinder enclosure. 

f). 

The LP cylinder valve should be readily accessible for hand 
operation. A door on the remote LP cylinder enclosure to gain 
access to the LP cylinder valve is acceptable, provided it is non- 
locking and can be opened without the use of tools.

If your, licensed contractor or licensed plumber, builds an LP cylinder 
enclosure following the guidelines in the ANSI Standard for Outdoor 
Cooking Gas Appliances, 
Z21.58 CSA 1.6, you need to order kit number (#21287), which will 
contain the hose and regulator assembly, mounting bracket for the 
regulator, connection fi ttings and LP tank bracket for retaining the LP 
cylinder that must be used with the Summit

®

 Built-In gas grill. The 

hose and regulator in the kit (#21287) is listed as part of the CSA listed 
Summit

®

 Built-In gas grill.

ASSEMBLY

Summary of Contents for SUMMIT 42390

Page 1: ...ich can cause serious bodily injury or death or damage to property WARNING 1 Do not store or use gasoline or other flammable liquids or vapors in the vicinity of this or any other appliance 2 An LP cy...

Page 2: ...pane gas is not natural gas The conversion or attempted use of natural gas in a liquid propane unit or liquid propane gas in a natural gas unit is dangerous and will void your warranty Do not attempt...

Page 3: ...xamination shall indicate to Weber s satisfaction they are defective Before returning any parts contact the Customer service representative in your region using the contact information sheet provided...

Page 4: ...cylinder enclosure the gas should not be allowed to vent or migrate into the empty or hollow area of the island Ventilation openings in the sidewalls of the enclosure should only communicate with the...

Page 5: ...he structure island counter tops and adjacent work areas for the LP Tank Enclosure must be built from noncombustible materials only NOTE If you have questions on what materials are considered noncombu...

Page 6: ...8 4 1 2 4 2 2 PARTS LIST Hose and regulator 1 Tank stand 1 Tank stand base 1 Tank Scale 1 1 4 20 nut 6 Nylon washer 12 1 4 20 x 1 2 bolt 6 Cylinder glide 2 1 2 Flare Gasket 2 3 8 Flare Gasket 2 ASSEMB...

Page 7: ...re before use MOUNTING HARDWARE NOT INCLUDED MOUNTING THE LP HOSE AND REGULATOR Securley mount the hose and regulator bracket to the top of the built in tank enclosure using non corrosive hardware MOU...

Page 8: ...de View back of box top of box 1 2 Flared Gasket 3 Use the 1 2 inch flared gasket to ensure proper seal NOTE Only use the 3 8 inch flared gasket if you are installing the optional side burner 4 Connec...

Page 9: ...water solution and a rag or brush to apply it 1 Turn the LP cylinder so the opening of the valve is either to the front side or rear of the Weber gas barbecue Lift and hook the cylinder onto the fuel...

Page 10: ...eck for gas leaks every time you disconnect and reconnect a gas fitting Note All factory made connections have been thoroughly checked for gas leaks The burners have been flame tested As a safety prec...

Page 11: ...er make sure you get a similar tank in return Your LP cylinder is equipped with a quick closing coupling or type 1 valve and an OPD Overfilling Prevention Device Other LP cylinders may not be compatib...

Page 12: ...PRODUCTS CO www weber com GAS INSTRUCTIONS If you have questions about spare LP cylinders contact Customer Service at 1 800 446 1071 All LP tank supply systems must include a collar to protect the cy...

Reviews: