NE Pumps.
9
Wire Size
A licensed electrician should be consulted to determine what wire size
should be used if more power is required. Consult the table for electrical
information.
Model
hp
V
Phases
rpm
Amps
(max.)
Amps
(max) at
locked
rotor
Winding
resistance
at Start-up
Cable
size
NE 4 45-4-220
4.5
220
3
1,750
18.2
56.0
1.43
10/4
NE 4 45-4-440
4.5
440
3
1,750
9.1
28.0
5.71
10/4
NE 4 75-4-220
7.5
220
3
1,750
26.8
80.0
0.71
10/4
NE 4 75-4-440
7.5
440
3
1,750
13.0
40.0
2.85
10/4
NE 4 113-4-220
11.3
220
3
1,750
28.0
126.0
0.43
10/4
NE 4 113-4-440
11.3
440
3
1,750
14.0
63.0
1.72
10/4
NE 4 150-4-220
15.0
220
3
1,750
38.0
160.0
0.35
8/4
NE 4 150-4-440
15.0
440
3
1,750
19.0
80.0
1.45
8/4
NE 6 90-6-220
9.0
220
3
1,150
36.0
162.0
0.445
2/5
NE 6 90-6-440
9.0
440
3
1,150
18.0
81.0
1.780
2/5
NE 6 180-6-220
18.0 220
3
1,150
50.0
232.0
0.080
2/5
NE 6 180-6-440
18.0 440
3
1,150
25.0
116.0
0.320
2/5
NE 6 240-6-220
24.0 220
3
1,150
64.0
290.0
0.235
2/5
NE 6 240-6-440
24.0 440
3
1,150
32.0
145.0
0.940
2/5
NE 6 300-6-220
30.0 220
3
1,150
82.0
364.0
0.123.
2/5
NE 6 300-6-440 30.0 440
3
1,150
41.0
182.0
0.490
2/5
NE 6 180-4-220
18.0
220
3
1,750
50.6
232.0
0.270
2/5
NE 6 180-4-440
18.0
440
3
1,750
25.3
116.0
1.080
2/5
NE 6 240-4-220
24.0
220
3
1,750
62.8
290.0
0.205
2/5
NE 6 240-4-440
24.0
440
3
1,750
31.4
145.0
0.820
2/5
NE 6 300-4-220
30.0
220
3
1,750
76.0
364.0
0.188
2/5
NE 6 300-4-440
30.0
440
3
1,750
38.0
182.0
0.750
2/5
NE 6 360-4-220
36.0
220
3
1,750
90.0
434.0
0.110
2/5
NE 6 360-4-440
36.0 440
3
1,750
45.0
217.0
0.440
2/5
NE 6 480-4-440
48.0 440
3
1,750
65.0
290.0
0.540
2/5
NE 6 600-4-440
60.0 440
3
1,750
78.0
363.0
0.310
2/5
NE 6 750-4-440 75.0 440
3
1,750
96.0
576.0
0.187
2/5