Global peripherals
Global peripherals, as Extension Units (V, VI), Outdoor Sensor (VIII) and Commissioning Touch Screen (VII), collect and display
values that are used to control the entire Sentio system or are used to extend the Sentio system.
The global components have to be registered to the CCU. Usually they are automatically enrolled and registered at the
system startup. The only global component that is not automatically registered is the Wireless Outdoor Temperature Sensor.
It is registered following this way:
1. Press button F the CCU (IV) as long till the LED E is flashing red.
2. Insert the battery(s) into the outdoor temperature sensor. The LED E on the CCU now will glow green.
Local peripherals
Local peripherals, as room thermostats and room sensors, collect and display values for the room they are mounted in.
A total of 24 Local peripherals can be registered to one CCU.
Before the system can be used all local peripherals have to be registered to the channel(s) they have to control.
They are registered in the following way:
1. Press button F or K on the CCU (IV) until the LED next to the channel you want to register the thermostat/sensor
to is flashing red.
2. a) Wireless peripherals: Insert the batteries into the room thermostat / sensor (see manual added to the package)
b) Wired peripherals: Touch the room thermostat / sensor touch area and hold it for approx. 5 sec
(see manual added to the package).
When the CCU has received the enrollment code from the room thermostat / sensor the light next to the channel you
choose will switch to continuous on.
3. If more than one channel has to be registered to the same room thermostat / sensor, repeat step 1 and 2
Repeat the above for the other room thermostats / sensors to be registered.
If you have to remove a local peripheral from the system follow this steps:
1. Press button F or K on the CCU (IV) or Extension Unit (V, VI) until the desired channel flashes red.
2. Hold button H on the CCU (IV) or Extension Unit (V, VI). The LED next to the relevant channel turnes off.
Actuators
The actuators are supplied open and will not close until they have been activated for 10 minutes. If an output has not been
activated within two hours after starting the CCU, it will automatically activate the channel to close the actuator.
In total max. 16 acutators can be connected to a CCU/EU combination!
7
Summary of Contents for Sentio
Page 1: ...Control system Underfloor heating cooling WAVIN SENTIO Quick Guide January 2020...
Page 2: ...A A A F I H H H J L M N N L L N G G O K K F B B B C D E A...
Page 10: ...Enroll procedure thermostat sensors I...
Page 11: ...J Choose profile System Installer settings Hardware profile Change profile 3 2 4 1...