14
CLICK 516
•
USER GUIDE
Select the
516
tab from the menu and you will see two sub-tab as shown.
Figure 8 – Click 516 Subtabs
The Settings tab presents the following settings:
Setting
Description
Min Speed
This is the speed threshold that is used along with Top Occ to determine
if the Click 516 should enter HIOCC MODE. If the speed is in MPH or KPH
is determined by the SmartSensor HD.
Max Speed
This is the speed threshold that is used to determine if the Click 516
should enter NORMAL MODE. If the speed reported in the interval is
above this speed the module will enter NORMAL MODE.
Top Occ (Occupancy)
This is the Occupancy threshold that is used along with the Min Speed to
determine if the Click 516 should enter HIOCC MODE. The Speed of the
interval must be below the Min Speed and the Occupancy of the interval
must be above the Top Occ for the Click 516 to enter HIOCC MODE
Sensor Port
Select the port that is connected to the SmartSensor HD. 232TOP and
485TBUS are the only options.
Poll Interval
Enter the number of milliseconds you want the Click 516 to wait before
it polls for Interval data. The longer the interval the bigger this number
can be.
Poll Event
Enter the number of milliseconds you want the Click 516 to wait before it
polls for Event Data. This number should be kept short to make sure the
data gets sent to the Click Contact Closure cards as real time as possible.
Table 2 – Description of Settings Tab