background image

5.  Validate Installation

Check the lights

The lights on the face of the Auditor help to validate that the     

device is operating.
•   L1, L2, L3 - Indicate the initialisation and communications status    

of the Auditor.

•   MB - indicates the Modbus communications status.
The installation is completed successfully when all indicators are lit 

solid green:
•   Indicators L1, L2 and L3. 

The table below shows the meaning of lights.

Modbus Indicator (MB)

Support

Need help with your installation?

Our team is available from 09:00 to 17:00, Monday to Friday AEDT 

Support phone: 02 8316 7540 (+61 2 8316 7540 from overseas) 

Support: For additional materials and to lodge a Support ticket, 
please visit: 

www.wattwatchers.com.au/support

L1

L2

L3

Explanation

Powered off

Powering on

Powered on  

Searching for SIM

SIM found

Waiting for servers 

Connection complete

Green

Modus connection is working. Blinks 

off briefly when there is activity

Flashing 

red

Not communicating - may mean 

cable not connected properly, slave 

powered off, or device not supported

Summary of Contents for Auditor 6M+MB

Page 1: ... site 1 Before you begin 2 Connect power and Modbus 3 Connect your CTs 4 Use the onboarding tool 5 Validate that your installation is correct Auditor 6M MB Cellular monitoring with Modbus Check here for latest documents www wattwatchers com au support Part WW018060 August 2020 ...

Page 2: ...it the Auditor Do you have 3G 4G signal inside the switch box Do you have a smartphone or tablet with internet to configure the device Do you have the necessary electrician tools to install including energy measurement clamp meters for testing Have you ensured that the install complies with the electrical standards in your jurisdiction including an isolation circuit breaker either existing or new ...

Page 3: ...e Voltage Connections Use this configuration when one phase is present The voltage connections are labelled P1 P2 P3 N Connect P1 P2 P3 to the same phase Connect neutral to N Connect the Modbus cable The Auditor operates as a Modbus master for devices where a driver has been developed Make Modbus connections D Connect to D on the slave device D Connect to D on the slave device S Connect to the shi...

Page 4: ...nnected to the bottom of the Auditor Only Wattwatchers CT s are supported The CT connections are labelled 6 5 4 3 2 1 The white wires connect to terminals labelled three wires in each terminal The pink wires connect to the terminals labelled The CTs and Voltage phases must match as stated below CT connected to cables connected to 1 and 4 P1 2 and 5 P2 3 and 6 P3 It is acceptable to use less than s...

Page 5: ... and setup your Auditor installation The onboarding setup tool provides a series of steps to capture details of your setup and provide real time feedback on the success of the installation The onboarding setup tool MUST be used for each and every Auditor installation onboarding wattwatchers com au ...

Page 6: ... Modbus Indicator MB Support Need help with your installation Our team is available from 09 00 to 17 00 Monday to Friday AEDT Support phone 02 8316 7540 61 2 8316 7540 from overseas Support For additional materials and to lodge a Support ticket please visit www wattwatchers com au support L1 L2 L3 Explanation Powered off Powering on Powered on Searching for SIM SIM found Waiting for servers Connec...

Reviews: