UNIT DESCRIPTION AND OPERATION

The WS‑301 and WS‑301‑347 PIR Wall Switch Occupancy Sensors turn lighting 

or fan loads ON and OFF based on occupancy and ambient light level. They are 

designed to replace a standard light switch. The WS‑301 operates with 120 or 

277VAC line voltage and the WS‑301‑347 operates with 347VAC line voltage. All 

other features are the same in both models. (Throughout this manual, “WS” is 

used to indicate either sensor.)
The sensor uses passive infrared technology to sense human motion, and 

defines it as occupancy. A red LED on the sensor blinks upon occupancy and 

then resets. It will blink again when it detects motion after the 2‑second reset.
The sensor turns ON the load automatically when it detects occupancy. 

Once the space is vacant and the time delay elapses, it turns OFF the load 

automatically. 
If adequate ambient light is already present in the area, the sensor will hold 

OFF the load it controls. When the light drops below a field selectable level and 

the sensor detects occupancy, the sensor turns ON the load. Once turned ON, 

the load remains ON until the space is vacant or the light level rises above the 

setpoint and the time delay expires. 

Manual Operation:  

The occupant can press the ON/OFF button to turn the load 

ON and OFF. When the load is turned ON manually, the sensor will keep the 

load ON until no motion is detected for the length of the time delay. If the load 

is turned OFF manually, the 

sensor holds the load OFF until 

no motion has been detected for 

the duration of 5 minutes. The 

next time the sensor detects 

occupancy and the ambient light 

is lower than the set level, the 

sensor automatically turns ON 

the load.

Walk‑test feature:

When the Time Delay trimpot 

is in the fully counterclockwise 

position, the sensor has a 30 

second time delay. This allows 

you to quickly check the sensor 

coverage area.

Service function:

In the event of unit failure or if 

it is necessary to leave the load 

ON, remove the Service Jumper plug. This disables all automatic ON and OFF 

functions and the load can only be operated using the ON/OFF button.

Call 800.879.8585 for Technical Support

ON/OFF
Switch

Service
Jumper

Light Level
Time Delay
Sensitivity

LED

Fresnel Lens

ON/OFF Button
(Switch Cover)

 

Press down

on tab and

pry off Cover

(L)
(T)
(S)

Maximum =  clockwise

Minimum =  counterclockwise 

Summary of Contents for WS-301

Page 1: ...allast E ballast LED 1 4 hp WS 301 347 Voltage 347VAC 50 60Hz Load Requirements 0 1500W ballast LED 1 4 hp Common Features Time Delay Adjustment 30 seconds 30 minutes Sensitivity Adjustment Minimum Maximum Light Level Adjustment 0 200fc 4000K Operating Temperature 40oC 104oF Storage Temperature 70oC 158oF Terminal screw torque 16 lbf in 18 kgf cm Optional Neutral Connection Installation Instructio...

Page 2: ...d ON the load remains ON until the space is vacant or the light level rises above the setpoint and the time delay expires Manual Operation The occupant can press the ON OFF button to turn the load ON and OFF When the load is turned ON manually the sensor will keep the load ON until no motion is detected for the length of the time delay If the load is turned OFF manually the sensor holds the load O...

Page 3: ...le in the space in order to detect occupancy Obstructions such as furniture blocking the sensor s lens may prevent occupancy detection 15 4 6m 35 10 7m 4 0 1 2m 35 10 7m floor Opaque adhesive tape is supplied so that sections of the sensor s view can be masked This allows you to eliminate coverage in unwanted areas Since masking removes bands of coverage remember to take this into account when tro...

Page 4: ...d turns ON after the warm up period ends if the sensor detects motion Rapid successive pressing of the ON OFF button causes a delay in function A single press of the button causes an immediate response If the button is pressed again within 2 seconds the switch ignores it if there is not enough power Wait at least two seconds between button presses 5 Install industry standard decorator wall switch ...

Page 5: ... LOAD to Red flying lead 2 LINE to Black flying lead 3 GROUND to Green Visit our website for FAQs www wattstopper com Load Red Black Green Neutral Optional Neutral to Line Single level wiring Load Load Green Red Black Neutral Optional Neutral to Line Manual bi level lighting wiring ...

Page 6: ...e light level at maximum fully clockwise a Set the Time Delay to the walk test position fully counterclockwise b Set the Light level to 50 12 o clock position which is approximately 100fc Let the sensor time out so lights are OFF Enter the space and lights should remain OFF c Make sure your body does not cast a shadow on the sensor and adjust the light level trimpot clockwise in small increments d...

Page 7: ...hat the time delay is set to the desired delay and that there is no movement within the sensor s view for that time period To quickly test the unit for proper operation turn the time delay to minimum fully counterclockwise and move out of the sensor s view Load should turn OFF after 30 seconds If load still does not turn OFF call 800 879 8585 for technical support Sensing motion outside desired ar...

Page 8: ...attStopper warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or rein...

Reviews: