wattstopper WN-100 Installation Instructions Manual Download Page 4

INSTALLATION

Caution: A neutral connection is required for sensor operation.
A qualified electrician should be consulted regarding the availability of a
neutral in your particular installation.

1. Make sure that power has been

turned off at the circuit breaker.

2. Connect the existing wires to the

sensor terminals.
• Hot or Black to Line; 

Load or Red to Load; 
Ground or Green to Ground;
Neutral or White to Neutral.

• Do not allow any bare wire to

show above the connector.

3. Attach the sensor to the wall box

by inserting screws into the two
wide holes on the top and bottom
of the attached metal bracket. Line them up with the holes in the wall box
and tighten.

4. Turn on the circuit breaker. Push the ON/OFF button and the lights will

turn on.

TO

P

INDOOR 

USE 

ONL

Y

TO

P

INDOOR 

USE 

ONL

Y

Insert or wrap wire as shown. Tighten screw in the

clockwise direction.

CAUTION: TURN THE POWER OFF  

AT THE CIRCUIT BREAKER BEFORE WIRING.

Call 800.879.8585 or 972.578.1699 for Technical Support

Wire insert

Optional
wire wrap

Strip Gauge

#12 – #14 AWG

Cu Wire Only

Summary of Contents for WN-100

Page 1: ...cent and Compact Fluorescent Horsepower Rating 1 6 HP WN 100 277 Voltage 277VAC 60Hz Power Consumption 0 92W maximum Load Requirements 800W Fluorescent General Time Delay Adjustment Fixed 15 minute 30 minute 1 hour 2 hour Operating Temperature Range 32 131 F 0 55 C Operating Humidity Range 95 RH non condensing Installation Instructions US Patent Number 4 787 722 ...

Page 2: ...y when motion is detected Automatic ON In Automatic ON mode the WN 100 automatically turns lights on when a designated space becomes occupied Note In both Manual ON and Automatic ON the ON OFF button turns lights off The ON OFF button must be pressed again to turn lights back on Time Delay The WN 100 automatically turns lights off after a space becomes vacant and a preset time interval or time del...

Page 3: ...aintain its coverage capacity and optimally detect motion the WN 100 must have a clear and unobstructed view 4 0 1 2m 25 7 6m floor Hot Black Neutral White Load Load Red Neutral White TOP INDOOR USE ONLY ON 1 Ground Green Single sensor wiring 25 7 6m 10 3 1m WIRING Visit our website for FAQs www wattstopper com ...

Page 4: ... allow any bare wire to show above the connector 3 Attach the sensor to the wall box by inserting screws into the two wide holes on the top and bottom of the attached metal bracket Line them up with the holes in the wall box and tighten 4 Turn on the circuit breaker Push the ON OFF button and the lights will turn on TOP INDOOR USE ONLY TOP INDOOR USE ONLY Insert or wrap wire as shown Tighten screw...

Page 5: ...n the WN 100 will operate in Test Mode for five 5 minutes During this period the time delay will be 15 seconds and the WN 100 will operate as Automatic ON After five 5 minutes the WN 100 will use the parameters of the selected mode Note Do not leave the Program Mode Switch in the UP Program position The WN 100 will only operate properly in the DOWN End User position Mode Selections Flashes Time De...

Page 6: ...tion The load should turn off within 15 seconds and the nightlight should subsequently turn on Repeat as necessary to ensure that the desired coverage areas are within detection range Lights will not turn on nightlight is illuminated 1 Press ON OFF button lights should turn on If not check sensor wire connections to the load 2 Check the lamp Lights will not turn on nightlight is NOT illuminated 1 ...

Page 7: ...G INFORMATION WARRANTY INFORMATION Watt Stopper Legrand warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of Watt Stopper Legrand for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property rev...

Reviews: