background image

Note: For multi‑way operation of two or more RD‑250s, it is recommended to set 

to the same values the Operating Mode and the Time Delay adjustments in all 

sensors related to the same load.
1.  Firmly grasp the side edges of the Lock 

Bar and gently pull it away from the 

switch face until it clicks. Do NOT attempt 

to pull the Lock Bar off of the switch!

2.  Firmly grasp the side edges of the 

ON/OFF/DIM button. Slide the button 

downward approximately 1/2 inch to 

expose the mode button and adjustment 

dials.

Setting up the Operating Mode

Select the operating mode by pressing the 

Mode button. The amber LED behind the 

switch button blinks to indicate the selected 

mode:
•  One blink indicates Mode 1 (Vacancy 

Sensor Operation), Manual‑ON/OFF, 

Auto‑OFF

•  Two blinks indicate Mode 2 (Occupancy 

Sensor Operation), Auto‑ON/OFF with 

manual control and reset to auto (after 5 minutes of vacancy). 

To change the operating mode, press the Mode button. The LED blinks to indicate 

the selected mode. It repeats the selected mode three times. After that, the unit 

operates in the indicated mode.

Adjusting the Time Delay

Turn the right dial counter‑clockwise to reduce the amount of time the lights will 

remain on after the last motion detection (minimum = 15 seconds). Turn the same 

dial clockwise to increase this time delay (maximum = 30 minutes). You can only 

select the following values: 15 seconds/5 minutes/15 minutes/30 minutes.

Warning: Do not overturn the Time Delay adjustment dial!

Adjusting the Light Level

This feature is factory set at maximum, so that even the brightest light will not 

prevent the sensor from turning the load ON when it detects occupancy. If this 

feature is not needed, leave the light level at maximum, fully clockwise. The light 

level must be adjusted when lights would normally be turned OFF because there 

is enough natural illumination. Each RD‑250 may have a different light level 

setting.
1. Set all RD‑250s to Mode 1 (Manual‑ON) ‑ except for the one that you’re 

adjusting.

  Set the RD‑250 you’re adjusting so that it is in Mode 2 (Automatic‑ON).
2.  Reduce the time delay to 15 seconds.
3.  Adjust the Light Level dial to minimum (fully counter‑clockwise) on the unit 

that you’re adjusting. Move out of the coverage area. Let the sensor time out 

so lights are OFF and then wait 30 seconds more.

4.  Without casting a shadow on the sensor, enter the area. The lights should 

remain OFF. Adjust the Light Level dial clockwise in small increments. After 

each adjustment, wait 5‑10 seconds to see if the lights turn ON.

  Continue this procedure until the lights turn ON. At this setting the light will 

not turn ON automatically with occupancy if the light level measured at this 

sensor is above the current natural illumination.

5.  Repeat the process (beginning with step 1) for each RD‑250 in your multi‑way 

configuration until the Light Level has been adjusted properly in all of them.

6.  When you have finished adjusting the Light Level of all the RD‑250s, return 

them all to Mode 2.

7.  Reset the time delay to the desired setting in all units.

Warning: Do not overturn the Light Level adjustment dial!

TEST MODE

To test the detection coverage:
1.  Press and hold the ON/OFF/DIM button. After 10 seconds the lighted switch 

turns off. The load turns ON if it was not already ON. The sensor is now in 

a TEST mode that lasts 5 minutes. (You can end the TEST mode sooner by 

Lock Bar

Mode Button

& Adjustment

Dials

Slide down

On/Off/Dim

Button

Air Gap Switch

Time Delay

30

 

   

Mi

n.

Se

c.

15

 

Min.

5

Min.

ma

x

mi

n

Mode

 

15

Light

Level

06006r 1

1- Manual

2- Auto-O N

Fig. 5: Sensor Adjustment Controls

www.wattstopper.com

Summary of Contents for RD‑250

Page 1: ... the dimmable load ON the RD 250 recalls the last used dimming level While the sensor is factory preset as a Vacancy Sensor with manual ON operation it can be adjusted to work as an Occupancy Sensor that turns the controlled load ON automatically upon detection of occupancy in the area The RD 250 can be wired with up to 3 additional RD 250s for multi way Manual Auto ON OFF of one or several loads ...

Page 2: ...F DIM button can be used to manually turn ON and OFF the lighting load and to dim it UP and DOWN To turn the load ON tap firmly on the ON OFF DIM button once The amber LED turns OFF and the load turns ON to the last used dimming level The lighting load may or may not appear to be ON depending on how low the lights were set the last time they were dimmed Once the load has been turned ON push and ho...

Page 3: ...ted to the existing switch so that they can be identified later Disconnect the wires Make sure the insulation is stripped off of the wires to expose their copper cores to the length indicated by the Strip Gage in Fig 3 approx 1 2 inch For your safety Connecting a proper ground to the sensor provides protection against electrical shock in the event of certain fault conditions If a proper ground is ...

Page 4: ... the auxiliary RD 250 and to the TRAVELER 1 wire Connect the TRAVELER 1 wire from the black wire of the auxiliary RD 250 to the black wire of the master RD 250 Connect the lamp power LOAD to the red wire on the master RD 250 Cap the red wire on the auxiliary RD 250 Connect the TRAVELER 2 wire coming from the yellow wire of another RD 250 to the yellow wire of the RD 250 that you are wiring AUXILIA...

Page 5: ...em with the lens positioned above the ON OFF DIM button lens at top ON OFF DIM button at bottom Secure to the wall box with the screws provided 6 Make any necessary adjustments See the SENSOR ADJUSTMENT PROGRAMMING section for information 7 Install cover plate Install industry standard decorator wall switch cover plate not included 8 Restore power to the circuit Turn on the breaker or replace the ...

Page 6: ...level at maximum fully clockwise The light level must be adjusted when lights would normally be turned OFF because there is enough natural illumination Each RD 250 may have a different light level setting 1 Set all RD 250s to Mode 1 Manual ON except for the one that you re adjusting Set the RD 250 you re adjusting so that it is in Mode 2 Automatic ON 2 Reduce the time delay to 15 seconds 3 Adjust ...

Page 7: ...s maximum TROUBLESHOOTING Check the position of the Air Gap Switch on all RD 250s before beginning troubleshooting Lighted switch is OFF no load response to ON OFF DIM button s press or to any of the RH 253 momentary wall switches if applicable Make certain that the circuit breaker is on and functioning Lighted switch is ON no load response to ON OFF DIM button s press or to any of the RH 253 mome...

Page 8: ...roubleshooting turn OFF power to the circuit then check wire connections or call technical support COVER PLATES WattStopper RD wall switches fit behind industry standard decorator style switch cover plates WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and workmanship for a period of five 5 years There are no obligations or liabilities on the part of Wa...

Reviews: