Step 5 

Attach the ground wire.

Step 6 

Connect the Power Supply to the LMPI board.

Red

Black

Step 7 

Connect one or more LMRJ cables to the RJ45 jacks. There are two DLM IRB networks (labeled A & B) used to connect DLM devices such 

as the LMFC-011 Fixture Controllers, switches, sensors, and room controllers. The networks are labeled A and B. Each network has two 

RJ-45 jacks, for connecting CAT5 cable. It is not important which of the two jacks are used. 

Note: 

RJ45 jacks/Cat5 cables are only used to connect to DLM switches, sensors, room controllers, etc. to the panel. To connect one 

panel to another panel, use the MS/TP connectors
Once installation is complete, re-attach the cover to the LMCZ-301.

Network A

Network B

IR for LMCT 
Communication

MS/TP Connector for 

Segment Network

Power

Connection

Optional Installation of LMRC-100

In situations where a larger number of devices 

are connected to a DLM network, you can 

increase the amount of power output from 

the LMZC-301 by installing a powered room 

controller on either Cat 5e network (which 

adds power to just that network), or by 

installing one or two LMRC-100s within the 

unit (one per network). Secure the LMRC-100 

to the power supply board on the LMZC-301, 

as shown to the right. Then, connect an LMRJ 

cable from the LMRC-100 to the LMZC-301.

Note: 

If using an LMRC-100, maximum 

operating condition is 104 F (40 C)

Knock out for mounting second LMRC-100

Note: 

An LMRC-100 should be only 

connected to Network A 

or

 B only. To 

use both Networks, you will need to 

install two LMRC-100s.

WattStopper recommends 

using grommets to protect 

CAT5 cables routed 

through knock out holes