Ins
tallation Ins
tructions
LMZC-301
DLM Zone Controller
Step 1
Remove the P115/277 board with the LMPI assembly
Step 2
Mount the LMCZ-301, using 4 mounting screws.
Step 3
Reinstall the P115/277 board with the LMPI assembly
Note:
If installing an optional LMRC-100s, attach it to the
power supply board before reinstalling. See the instructions
at the bottom of the following page.
Step 4
Connect the incoming power cable to the power supply (and if used,
to the LMRC-100).
Green
(Ground)
White
(Neutral)
Black
(Line)
Black
(Line)
Green
(Ground)
White
(Neutral)
Connect as shown below for 115V
Connect as shown below for 277V
SPECIFICATIONS
Input voltage ..................................................115/277V 60 Hz
Class 2 connection to two independent DLM local networks (IRB)
24VDC output, up to 250mA across 2 RJ45 ports per
local network (A and B networks, 250 mA each)
If using an optional LMRC-100 to boost output, the
amount is 400 mA per network (two LMRC-100s
needed if using both networks)
Free-topology DLM local network segments may include
LMFC-011 Fixture Controllers, DLM switches, occupancy
sensors, daylight sensors and input modules
Category 5e cable, up to 1,000 ft. total per local network
Terminals for connection to DLM segment network
(BACnet MS/TP)
Segment network parameters
WattStopper LM-MSTP wire
Linear topology; 4000 ft. maximum per segment
Operating conditions:
for indoor use only ...................... 32-122 F (0 – 50 C)
........................................5-95% RH, non-condensing
UL and cUL listed
Green
(Ground)
White
(Neutral)
Black
(Line)
Green
(Ground)
White
(Neutral)
Black
(Line)
Wiring for an LMRC-100
Wiring for two LMRC-100s