LMZC-301

DLM Zone Controller

Step 1 

Remove the P115/277 board with the LMPI assembly

Step 2 

Mount the LMCZ-301, using 4 mounting screws.

Step 3 

Reinstall the P115/277 board with the LMPI assembly

Note: 

If installing an optional LMRC-100s, attach it to the 

power supply board before reinstalling. See the instructions 

at the bottom of the following page.

Step 4 

Connect the incoming power cable to the power supply (and if used, 

to the LMRC-100).

Green

(Ground)

White

(Neutral)

Black

(Line)

Black

(Line)

Green

(Ground)

White

(Neutral)

Connect as shown below for 115V

Connect as shown below for 277V

SPECIFICATIONS

Input voltage ..................................................115/277V 60 Hz

Class 2 connection to two independent DLM local networks (IRB)

 

24VDC output, up to 250mA across 2 RJ45 ports per 

 

local network (A and B networks, 250 mA each)

 

If using an optional LMRC-100 to boost output, the  

 

amount is 400 mA per network (two LMRC-100s 

 

needed if using both networks)

Free-topology DLM local network segments may include 

LMFC-011 Fixture Controllers, DLM switches, occupancy 

sensors, daylight sensors and input modules

Category 5e cable, up to 1,000 ft. total per local network

Terminals for connection to DLM segment network  

(BACnet MS/TP)

Segment network parameters

 

WattStopper LM-MSTP wire

 

Linear topology; 4000 ft. maximum per segment

Operating conditions:

 

for indoor use only  ...................... 32-122 F (0 – 50 C)

 

 ........................................5-95% RH, non-condensing

UL and cUL listed

Green

(Ground)

White

(Neutral)

Black

(Line)

Green

(Ground)

White

(Neutral)

Black

(Line)

Wiring for an LMRC-100

Wiring for two LMRC-100s