2

PLUG N’ GO OPERATION (PNG)

All loads are bound to all buttons and the dimmer paddle on the LMSW-105-CCT. 
To change the recorded CCT levels for any button, simply adjust the lights in the room to the desired levels and 

then press and hold the desired button for 5 seconds.
The percent corresponds to a CCT value of Max-Min * %.

UNIT ADJUSTMENT - PUSH N’ LEARN (PNL)

Load Selection Procedure

A configuration button allows access to our patented Push n’ Learn™ technology to change the binding relationship between control 

devices and loads.

Step 1 Enter Push n’ Learn

1.  Using a pointed tool, press and hold the configuration button for 3 seconds, until the Red LED on the switch 

begins to blink. 

2.  When you release the configuration button, the red LED on other communicating DLM Local Network 

devices begins to blink rapidly. 

3.  The DLM Local Network is now in PnL mode. The Red LEDs continue to blink until you exit PnL mode.
4.  All loads in the room turn OFF after entering PnL. After one second, one load turns ON. This is Load #1, 

which is bound to the LMSW-105-CCT paddle and all buttons as part of the Plug n’ Go factory default 

setting. The Blue LED will be ON bright for all switch buttons, dimmers, scene buttons and sensors that are 

bound to this load.

Step 2 Load selection

1.  Press and release the configuration button to step through the loads connected to the DLM Local Network. 

As each load turns ON note which devices (dimmers, scene and switch buttons and sensors) are showing 

the blue LED. These devices are currently bound to the load that is ON.

2.  To unbind a button from a load, press the button while its blue LED is ON. The blue LED turns OFF to indicate 

the button no longer controls the load that is currently ON. On the scene switch, unbinding a load from a scene 

button removes it from the scene so that when the scene activates the load’s state does not change.

3.  Pressing the switch button again while the load is ON rebinds the load to the button and the blue LED 

illuminates.

Step 3 Exit Push n’ Learn

1.  Press and hold the configuration button until the red LED turns off, approximately 3 seconds.

TROUBLESHOOTING

Loads do not operate as expected.

Switch button or rocker 

paddle LEDs don’t light

1.  Check to see that the the switch is connected to the DLM Local Network.
2.  Check for 24VDC input to the switch: Plug in a different DLM device at the switch location. If the 

device does not power up, 24VDC is not present.
•  Check the high voltage connections to the room controller.
•  If high voltage connections are good and high voltage is present, recheck DLM Local Network 

connections between the switch and the room controller.

The wrong lights are 

controlled

1.  Configure the switch buttons to control the desired lights using the Push n’ Learn adjustment 

procedure.

Button or rocker paddle 

doesn’t actuate

1.  Make sure the switch frame and button are assembled properly.
2.  Make sure that the wall plate is not pinching the frame.

LEDs turn ON and OFF 

but load doesn’t switch

1.  Make sure device is not in PnL.
2.  Check load connections to room controller.

 

 

 

 

 

 

 

 

 

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.  

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 –  

IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Default CCT

level
100%K

75%K

50%K

25%K

Summary of Contents for LMSW-105-CCT

Page 1: ...attstopper room controllers and also available at www legrand us wattstopper Installation shall be in accordance with all applicable regulations local and NEC codes Wire connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring To be connected to a Class 2 power source only Do not reclassify and install as Class 1 or Power and...

Page 2: ...s ON 2 To unbind a button from a load press the button while its blue LED is ON The blue LED turns OFF to indicate the button no longer controls the load that is currently ON On the scene switch unbinding a load from a scene button removes it from the scene so that when the scene activates the load s state does not change 3 Pressing the switch button again while the load is ON rebinds the load to ...

Page 3: ...lisé Pour les dispositifs DLM de classe 2 et le câblage du dispositif Doit être connecté à une source d alimentation de classe 2 seulement Ne pas reclasser et installer en tant que classe 1 ou en tant que fil d alimentation ou d éclairage Ne pas appliquer de solvant de nettoyage directement sur l appareil Appliquer le solvant de nettoyage sur un chiffon et frotter l appareil pour le nettoyer MONTA...

Page 4: ... s ÉTEINT pour indiquer que le bouton ne contrôle désormais plus la charge qui est actuellement ALLUMÉE Pour empêcher un dispositif d éclairage de s allumer couper le lien entre une charge et un bouton d ambiance sur un bouton d ambiance ainsi l état de charge ne sera pas modifié 3 En appuyant sur le bouton de l interrupteur à nouveau pendant que la charge est ALLUMÉE la charge sera à nouveau liée...

Page 5: ...ción para cubrir una caja de conexiones con circuitos de alimentación e iluminación o de Clase 1 3 BOTONES E INDICADORES El LED basculante está siempre encendido si el dispositivo LMSW 105 CCT está vinculado a una carga que está habilitada para CCT Cuando el nivel del Botón CCT preestablecido coincida con el CCT de la red DLM el LED brillará CONECTIVIDAD Y CABLEADO La ilustración siguiente muestra...

Page 6: ...espués de un segundo se encenderá una carga Esta es la carga N 1 que está vinculada con la paleta del LMSW 105 CCT y con todos los botones como parte de la configuración predeterminada de fábrica de Plug n Go El LED azul se mostrará encendido en todos los botones del interruptor los atenuadores los botones de escena y los sensores vinculados a esta carga Paso 2 Selección de carga 1 Presione y suel...

Reviews: