COVERAGE PATTERN
Do not obstruct the lens.
4 ft
40 ft
40 ft
25 ft
25 ft
SIDE
VIEW
TOP
VIEW
25 ft
40 ft
180°
Major motion
Minor motion
5 ft
35 ft
35 ft
Quick St
art Guide
LMPW-101/102
Digital Lighting Management
PIR Occupancy Sensor
Line
Voltage
Room
Controller
J-Boxes
Daylight Sensor
Switch
LMPW-101
Switch
Corner Mount
Sensor
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Loads
2
1
Line/Hot
Black wire
Neutral
White wire
Red wire
to Load A (1)
Yellow wire
to Load B (2)
LMRC
102
Room
Controller
J Box
Corner Mount
Occupancy
Sensor
LMPW
Sensor
Switch
To
Load/Line
(Class 1 wiring)
DLM Local Network
(low voltage, Class 2)
LMRJ Cables
CONNECTIVITY
The illustrations below show examples of free-topology wiring. The LMPW communicates
to all other Digital Lighting Management devices connected to the low voltage DLM Local
Network, regardless of their position on the DLM Local Network.
Voltage ...............................................................................24VDC
Current Consumption ............................................................ 8mA
Power Supply .............. Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network ...................2 RJ-45 ports
DLM Local Network Characteristics:
Provides low voltage power over Cat 5e cable (LMRJ).
Supports up to 24 communicating devices, including 4
LMRC-10x or LMPL-101 max per each DLM Local Network.
Free topology up to 1,000ft of low voltage cable.
Environment ................................................. For Indoor Use Only
Operating Temperature ....................32° to 131°F (0° to 55°C)
Storage Temperature ...................... 23° to 176°F (-5° to 80°C)
Relative Humidity ...........................5 to 95% (non condensing)
Patent Pending
This unit is pre-set for Plug n’ Go™ operation,
adjustment is optional.
For full operational details, adjustment and more
features of the product, see the DLM System
Installation Guide provided with the DLM room
controllers and also available at
www.wattstopper.com
Installation shall be in accordance with all applicable
regulations, local and NEC codes.
To be connected to a Class 2 power source only.
Class 2 Device Wiring Only – Do Not Reclassify and Install
as Class 1, 3 or Power and Lighting Wiring.
Wire connections shall be rated suitable for the wire size (lead and
building wiring) employed.
Do not apply cleaning solvent directly onto unit. Apply cleaning
solvent onto a cloth, then wipe the unit to clean it.
Note: Plus 10
°
above horizon
MOUNTING
WARNING:
Do Not Install To Cover a Junction
Box Having Class 1, 3 or Power and Lighting
Circuits.
BUTTONS AND INDICATORS
Up
Down
Select
Configure
Button LED
LMPW-101
IR Window
PIR Detection LED
Sensor Binding LED
PIR Lens
Lens Release
Button
On/Off
LMPW-101 LMPW-102