COVERAGE PATTERN

Do not obstruct the lens. 

4 ft

40 ft

40 ft

25 ft

25 ft

SIDE

VIEW

TOP

VIEW

25 ft

40 ft

180°

Major motion
Minor motion

5 ft

35 ft

35 ft

Quick St

art Guide

LMPW-101/102

Digital Lighting Management

PIR Occupancy Sensor

Line

Voltage

Room

Controller

J-Boxes

Daylight Sensor

Switch

LMPW-101

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Loads

2

1

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load A (1)

Yellow wire

to Load B (2)

LMRC

102

Room

Controller

J Box

Corner Mount

Occupancy

Sensor

LMPW

Sensor

Switch

To

Load/Line

(Class 1 wiring)

DLM Local Network 

(low voltage, Class 2)

LMRJ Cables

CONNECTIVITY

The illustrations below show examples of free-topology wiring. The LMPW communicates 

to all other Digital Lighting Management devices connected to the low voltage DLM Local 

Network, regardless of their position on the DLM Local Network. 

Voltage  ...............................................................................24VDC
Current Consumption ............................................................ 8mA
Power Supply .............. Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network ...................2 RJ-45 ports 
DLM Local Network Characteristics: 

  Provides low voltage power over Cat 5e cable (LMRJ). 

  Supports up to 24 communicating devices, including 4  

  LMRC-10x or LMPL-101 max per each DLM Local Network. 

  Free topology up to 1,000ft of low voltage cable.
Environment ................................................. For Indoor Use Only
  Operating Temperature ....................32° to 131°F (0° to 55°C)
  Storage Temperature ...................... 23° to 176°F (-5° to 80°C)
  Relative Humidity ...........................5 to 95% (non condensing)
Patent Pending

This unit is pre-set for Plug n’ Go™ operation, 

adjustment is optional.

For full operational details, adjustment and more 
features of the product, see the DLM System 
Installation Guide provided with the DLM room 
controllers and also available at

 

www.wattstopper.com

Installation shall be in accordance with all applicable 

regulations, local and NEC codes.
To be connected to a Class 2 power source only.
Class 2 Device Wiring Only – Do Not Reclassify and Install
as Class 1, 3 or Power and Lighting Wiring.
Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed.
Do not apply cleaning solvent directly onto unit. Apply cleaning 

solvent onto a cloth, then wipe the unit to clean it.

Note: Plus 10

°

 above horizon

MOUNTING

WARNING:

 Do Not Install To Cover a Junction 

Box Having Class 1, 3 or Power and Lighting 

Circuits.

BUTTONS AND INDICATORS

Up

Down

Select

Configure

Button LED

LMPW-101

IR Window

PIR Detection LED

Sensor Binding LED

PIR Lens

  

Lens Release

       Button

On/Off

   LMPW-101                  LMPW-102

Reviews: