TROUBLESHOOTING

Loads do not operate as expected.

LEDs don’t light, display 

is off

1. Check to see that the the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location. 

If the device does not power up, 24VDC is not present.
•  Check the high voltage connections to the room controller.
•  If high voltage connections are good and high voltage is present, recheck DLM local 

Network connections between the sensor and the room controller.

The wrong lights are 

controlled

1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment 

procedure.

LEDs turn ON and OFF but 

load doesn’t switch

1. Make sure device is not in PnL.
2. Check load connections to room controller.

10/2014  

11434r2

Please 

Recycle

2800 De La Cruz Blvd.  

Santa Clara, CA 95050 

Phone: 800.879.8585 

www.wattstopper.com

MOUNTING

Rear
housing

4" Octagonal J-Box 
(at least 1.5" deep)

Front cover

Ceiling

Rear
housing

Front cover

Ceiling hole

LMRJ cable

LMRJ cable

Spring clips (2)

Screws

For applications requiring plenum rating

No box required in non-plenum rated applications

To octagon box:

Through ceiling tile:

WARNING: TO CONNECT A COMPUTER TO THE DLM LOCAL 

NETWORK USE THE LMCI-100.  NEVER CONNECT THE DLM LOCAL 

NETWORK TO AN ETHERNET PORT – DOING SO MAY DAMAGE 

COMPUTERS AND OTHER CONNECTED EQUIPMENT.

WARNING:

 A junction box used for sensor installation must not contain any Class 1, Class 3, or other power or 

lighting line voltage circuits

Load Parameters

Load 1

Loads 2-8 

or more

**

 

  

  

Plug Load

ON Mode
Operation*

AUTO-ON

MANUAL-ON

 

if switch is 

connected.

AUTO-ON

  

if no switch.

 

AUTO-ON

Blink Warning

OFF

OFF

OFF

Daylighting

ON

OFF

OFF

*   Auto-OFF is enabled according to the sensor Time 

Delay when a sensor is bound to the load, regardless 

of whether the load was turned on automatically with 

occupancy or manually using a switch.

**  Max 8 loads using LMRC-100 series room controllers.

FACTORY PRE-SET OPERATION

Sensor Parameters

T-DELAY

 

Time Delay 

20 minutes

Passive Infrared 

Sensitivity

90%

Ultrasonic Sensitivity

70%

W-T

Walk Through

OFF

TRIG

Initial Occupancy

PIR and 

Ultrasonic

RETRIG

Maintain Occupancy

PIR or 

Ultrasonic