TROUBLESHOOTING
Loads do not operate as expected.
LEDs don’t light, display
is off
1. Check to see that the the sensor is connected to the DLM local Network.
2. Check for 24VDC input to the sensor: Plug in a different DLM device at the sensor location.
If the device does not power up, 24VDC is not present.
• Check the high voltage connections to the room controller.
• If high voltage connections are good and high voltage is present, recheck DLM local
Network connections between the sensor and the room controller.
The wrong lights are
controlled
1. Configure the sensor to control the desired lights using the Push n’ Learn adjustment
procedure.
LEDs turn ON and OFF but
load doesn’t switch
1. Make sure device is not in PnL.
2. Check load connections to room controller.
10/2014
11434r2
Please
Recycle
2800 De La Cruz Blvd.
Santa Clara, CA 95050
Phone: 800.879.8585
www.wattstopper.com
MOUNTING
Rear
housing
4" Octagonal J-Box
(at least 1.5" deep)
Front cover
Ceiling
Rear
housing
Front cover
Ceiling hole
LMRJ cable
LMRJ cable
Spring clips (2)
Screws
For applications requiring plenum rating
No box required in non-plenum rated applications
To octagon box:
Through ceiling tile:
WARNING: TO CONNECT A COMPUTER TO THE DLM LOCAL
NETWORK USE THE LMCI-100. NEVER CONNECT THE DLM LOCAL
NETWORK TO AN ETHERNET PORT – DOING SO MAY DAMAGE
COMPUTERS AND OTHER CONNECTED EQUIPMENT.
WARNING:
A junction box used for sensor installation must not contain any Class 1, Class 3, or other power or
lighting line voltage circuits
Load Parameters
Load 1
Loads 2-8
or more
**
Plug Load
ON Mode
Operation*
AUTO-ON
MANUAL-ON
if switch is
connected.
AUTO-ON
if no switch.
AUTO-ON
Blink Warning
OFF
OFF
OFF
Daylighting
ON
OFF
OFF
* Auto-OFF is enabled according to the sensor Time
Delay when a sensor is bound to the load, regardless
of whether the load was turned on automatically with
occupancy or manually using a switch.
** Max 8 loads using LMRC-100 series room controllers.
FACTORY PRE-SET OPERATION
Sensor Parameters
T-DELAY
Time Delay
20 minutes
Passive Infrared
Sensitivity
90%
Ultrasonic Sensitivity
70%
W-T
Walk Through
OFF
TRIG
Initial Occupancy
PIR and
Ultrasonic
RETRIG
Maintain Occupancy
PIR or
Ultrasonic