background image

Quick St

art Guide

SENSOR PLACEMENT (10’ MAX. HEIGHT)

CONNECTIVITY

The illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital Lighting 

Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network. 

LMDC-100

Digital Lighting Management

Dual Technology

 

Ceiling Mount

 

 Occupancy Sensor

Sensor

25'

25'

Strong air

supply

6’

Sensor

Mount sensor at least 6’ away from air supply.
Avoid obstacles that block sensor’s line-of-sight.

Pendant
fixture

Line

Voltage

Room

Controller

J-Boxes

Daylight Sensor

Switch

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

Loads

2

1

Line/Hot

Black wire

Neutral

White wire

Red wire

to Load A (1)

Yellow wire

to Load B (2)

LMRC

102

Room

Controller

J Box

Ceiling Mount

Occupancy

Sensor

Switch

To

Load

Voltage: .....................................................................................24VDC

Current Consumption: ...............................................................20mA

Power Supply: ...................Watt Stopper/Legrand Room Controllers

Connection to the DLM Local Network ........................ 2 RJ-45 ports

DLM Local Network Characteristics:

 

Provides low voltage power over Cat 5e cable (LMRJ).

 

Supports up to 24 communicating devices, including 4 

 

LMRC-10x or LMPL-101 max per each DLM Local Network

 

Free topology up to 1,000ft of low voltage cable.

Environment .......................................................For Indoor Use Only

 

Operating Temperature ................. 32° to 131°F (0° to 55°C)

 

Storage Temperature ....................23° to 176°F (-5° to 80°C)

 

Relative Humidity ........................ 5 to 95% (non condensing)

Patent Pending

THIS UNIT IS PRE-SET FOR PLUG N’ GO™ 

OPERATION, ADJUSTMENT IS OPTIONAL.

For full operational details, adjustment and more 

features of the product, see the DLM System Installation 

Guide supplied with the LMRC-102 and also available at  

www.wattstopper.com

INSTALLATION SHALL BE 

IN ACCORDANCE WITH ALL 

APPLICABLE REGULATIONS, 

LOCAL AND NEC CODES.

Intended for Listed Class 2 DLM 

Devices.
For Class 2 DLM devices -  

To be connected to a Class 2 

power source only.

For Class 2 Device Wiring Only – 

Do Not Reclassify and Install as 

Class 1, or Power and Lighting 

Wiring.
Wire connections shall be rated 

suitable for the wire size (lead 

and building wiring) employed.

25 ft

(7.62m)

25 ft x 25 ft

(7.62m x 7.62m)

COVERAGE PATTERN

The LMDC-100 provides a 360° coverage pattern.The 

coverage shown represents maximum coverage for 

walking motion at a mounting height of 10 feet.

PIR 

Coverage

Ultrasonic 

Coverage