Quick St
art Guide
SENSOR PLACEMENT (10’ MAX. HEIGHT)
CONNECTIVITY
The illustrations below show examples of free-topology wiring. The LMDC-100 communicates to all other Digital Lighting
Management devices connected to the low voltage DLM Local Network, regardless of their position on the DLM Local Network.
LMDC-100
Digital Lighting Management
Dual Technology
Ceiling Mount
Occupancy Sensor
Sensor
25'
25'
Strong air
supply
6’
Sensor
Mount sensor at least 6’ away from air supply.
Avoid obstacles that block sensor’s line-of-sight.
Pendant
fixture
Line
Voltage
Room
Controller
J-Boxes
Daylight Sensor
Switch
Switch
Corner Mount
Sensor
Ceiling Mount
Sensor
DLM Local Network
Low Voltage
LMRJ Cables
Loads
2
1
Line/Hot
Black wire
Neutral
White wire
Red wire
to Load A (1)
Yellow wire
to Load B (2)
LMRC
102
Room
Controller
J Box
Ceiling Mount
Occupancy
Sensor
Switch
To
Load
Voltage: .....................................................................................24VDC
Current Consumption: ...............................................................20mA
Power Supply: ...................Watt Stopper/Legrand Room Controllers
Connection to the DLM Local Network ........................ 2 RJ-45 ports
DLM Local Network Characteristics:
Provides low voltage power over Cat 5e cable (LMRJ).
Supports up to 24 communicating devices, including 4
LMRC-10x or LMPL-101 max per each DLM Local Network
Free topology up to 1,000ft of low voltage cable.
Environment .......................................................For Indoor Use Only
Operating Temperature ................. 32° to 131°F (0° to 55°C)
Storage Temperature ....................23° to 176°F (-5° to 80°C)
Relative Humidity ........................ 5 to 95% (non condensing)
Patent Pending
THIS UNIT IS PRE-SET FOR PLUG N’ GO™
OPERATION, ADJUSTMENT IS OPTIONAL.
For full operational details, adjustment and more
features of the product, see the DLM System Installation
Guide supplied with the LMRC-102 and also available at
www.wattstopper.com
INSTALLATION SHALL BE
IN ACCORDANCE WITH ALL
APPLICABLE REGULATIONS,
LOCAL AND NEC CODES.
Intended for Listed Class 2 DLM
Devices.
For Class 2 DLM devices -
To be connected to a Class 2
power source only.
For Class 2 Device Wiring Only –
Do Not Reclassify and Install as
Class 1, or Power and Lighting
Wiring.
Wire connections shall be rated
suitable for the wire size (lead
and building wiring) employed.
25 ft
(7.62m)
25 ft x 25 ft
(7.62m x 7.62m)
COVERAGE PATTERN
The LMDC-100 provides a 360° coverage pattern.The
coverage shown represents maximum coverage for
walking motion at a mounting height of 10 feet.
PIR
Coverage
Ultrasonic
Coverage