SWITCH ADJUSTMENT
Enter Settings Mode by pressing the Calibration Button
(located on the left, behind the faceplate).
• If no input occurs within four seconds the display
flashes then moves to the next setting.
• Press the Calibration Button to view the settings
without making changes.
• Press the
ON
/
OFF
button within four seconds to
change the setting.
DELAY:
5 min. to 12 hr.
DELAY sets the time-out period. The selections begin at
the currently set time (3 hours, default). When the time is
less than an hour, the time increases by 5 minutes each
time you press the ON/OFF button. When the time is more than an hour,
it increases by 15 minues. When the selection passes 12 hours, it
restarts the selection scrolling at 5 minutes.
Scroll:
UP or down (dn)
To have the user’s time override options decrease from a longer time to a shorter time, set
Scroll for
dn
(down). To increase from a shorter time to a longer time, set Scroll for
UP
.
FLASH:
ON or OFF
Sound:
ON or OFF
When the setting selection is complete the unit will either:
• Beep once and display END if the calibration button is being held; release the button to
continue.
• Beep three times while it displays END. This gives you a chance to press the
ON
/
OFF
button to restart the setting procedure.
If you don’t press either button within three seconds, the unit exits the Settings Mode and
resumes its previous state.
ON
1
TS-400-24
LCD Display
Call 800.879.8585 for Technical Support
WIRING
ON/OFF
Button
Calibration
Button
#16-#18
Insert wires as
shown and tighten
screw in the clock-
wise direction.