PLACEMENT GUIDELINES

Depending upon obstacles such as furniture or partitions, the area of coverage may 

be less or more than the sensing distances shown in the coverage pattern. This 

must be considered when planning the number of sensors and their placement. It 

is also recommended to place the sensor 4 to 6 feet away from air supply ducts as 

rapid air currents or the differences in temperatures may cause false activations.
Mount the sensor to the ceiling. The CI-300 and CI-300-1 are designed for a ceiling 

height of about 8-10 feet. Mounting above or below this range will significantly 

affect the coverage patterns. Be aware that as you decrease the mounting height, 

you decrease the range and increase the sensitivity to smaller motions. Conversely, 

when you increase the height, you increase the range and decrease the sensitivity 

to smaller motions. At heights of more than 

12-14 feet, you may start to significantly 

reduce sensitivity. As a general rule, each 

occupant should be able to clearly view the 

sensor.
Often the best location to install a CI- 300 in 

a closed office is off-center. Avoid placing 

a sensor directly in line with an open door 

through which it has a clear view out, as the 

sensor may detect people walking by. 

Masking the PIR Lens:

 Opaque adhesive tape is supplied so that sections of the PIR 

lens can be masked. This restricts the sensor’s view and allows you to eliminate PIR 

coverage in unwanted areas such as hallways outside of the desired coverage area. 

Since masking removes bands of coverage, remember to take this into account 

when troubleshooting coverage problems. 

Open Office Area Coverage:

 To get 

complete coverage in an open office area, 

install multiple sensors so that there is 

an overlap with each adjacent sensor’s 

coverage area. 
For open office areas with partitions it is 

best to place sensors over intersection of 

four workstations.
For large areas of coverage use multiple 

sensors. 

CI-205

12'

18'

CI-205

36'

36'

Summary of Contents for CI-300

Page 1: ...r Packs Isolated Relay Rating 1A 30VDC VAC Operating Temperature 32 to 131 F 0 to 55 C Light Level One Step Adjustment 10FC 300FC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if n...

Page 2: ...half wave rectified AC CI 300 sensors also have an isolated relay with Normally Open and Normally Closed contacts for interfacing with HVAC or EMS COVERAGE PATTERN The CI 300 provides a 360 coverage...

Page 3: ...ions At heights of more than 12 14 feet you may start to significantly reduce sensitivity As a general rule each occupant should be able to clearly view the sensor Often the best location to install a...

Page 4: ...nal on sensor Wiring ONE LIGHTING LOAD FOR OCCUPANCY CONTROL AND A SECOND LOAD FOR OCCUPANCY AND LIGHT LEVEL AMBIENT LIGHT CONTROL connect BLUE wire from power pack to Control Out terminal on sensor B...

Page 5: ...es White Black Red Line Voltage Wire Color Legend Wiring the ISOLATED RELAY The Isolated Relay is rated for 1A 30VAC VDC Connect the wires necessary to the application that requires this output Relay...

Page 6: ...ips 2 Blue Control Out Black 24V Low Voltage Class 2 Line Voltage Line Neutral Feed Through Power Pack Man Switch Red CI 300 Common Man Switch 24V Jumper Back of LVS 1 For low voltage momentary switch...

Page 7: ...ght Level pushbutton See Sensor Adjustment 2 Momentarily press the Light Level pushbutton Do not exceed 4 seconds The sensor enters setup mode as indicated by the rapidly flashing green LED The LED wi...

Page 8: ...ensor securely in place 6 Snap the front cover onto the sensor Using an Octagonal J Box 1 Pull the low voltage wires from the power pack into the J Box through the conduit knockout 2 Connect the low v...

Page 9: ...Time Delay is set for Test Mode using the 5 seconds SmartSet setting DIP switches 3 4 5 are OFF 3 Ensure that the Light Level is at default maximum See the Light Level Feature section of this document...

Page 10: ...thin the 30 second re trigger period Automatic On This mode uses occupancy as well as switch activation to turn the load ON A manual switch provides the following additional functionality a The load c...

Page 11: ...using SmartSet or you can select a fixed time delay SmartSet records occupancy patterns and uses this history to choose an optimal time delay from 5 to 30 minutes SmartSet behavior starts immediately...

Page 12: ...that high voltage is present to power pack If it is replace power pack PIR Activity LED flashes 1 If the sensor s Light Level feature has been turned on the lights connected to the Light Level Output...

Page 13: ...lay to minimum and allow the sensor to time out If the lights turn off the sensor is working properly see Sensor Adjustment for readjustment of sensor Unwanted Sensor Activations LED flashes Possible...

Page 14: ...120 250VAC S120 277 347E P Auxiliary Relay Pack 120 277VAC 60Hz 20A Ballast 347VAC 60Hz 15A Ballast WARRANTY INFORMATION WattStopper warranties its products to be free of defects in materials and work...