Inverter Display Abbreviation and Complete Name Reference Table
Abbreviation
Complete Name
Safety Set
Select the code that meet local regulatory requirements
Battery_ID Set
Select the battery model
Work Mode
Current work mode / work mode setting
Export Limit
On-grid export limit function switch
Feed in Grid
Set the percentage of the power that is allowed to feed to the grid
Reactive Modes
Reactive Power Mode
PF
"Under ""Reactive Mode" "The reactive power can be regulated by the parameter PF
(Power Factor)."
Qt
"Under ""Reactive Mode" "The reactive power can be regulated by the parameter Q-Var
limits (in %)."
Q(P)
"Under ""Reactive Mode" "The PF changes with the output power of the inverter."
Q(U)
"Under ""Reactive Mode" "The reactive power changes with the grid voltage"
Fixed Q
The reactive power ratio when the "Reactive Mode" is Qt.
On-Off Grid SW
Off-grid function switch (If turn it on, the inverter will automatically switch to off-grid
mode to ensure the back-up side power supply when the gird is abnormal or off, oth-
¬erwise, there is no output on the back-up side)
Relax OffGrid
Reduce the switching sensitivity of the On/Off-grid (applied to the places where the
grid is unstable or inverter always entered off-grid mode for some reasons)
Offgrid ReConn.
When the power grid is off, the inverter can automatically restart the back-up output
after a fault or overloading protection occurred if the Off-grid restart is ON. Oth-
er¬wise, the back-up output needs to be restarted manually
Load Shifting
Peakload shifting function switch
SetMaxGrid
Set max allowed power from grid (under the condition of Peakload Shifting is on)
OnGrid SocProt.
On-grid battery SOC (State of Charge) Protection
OnGrid EndSOC
End-of-discharge SOC of on-grid
OffGrid SocProt.
Off-grid SOC Protection
OffGrid EndSOC
End-of-discharge SOC of off-grid
Unbalan. Output
3-Phase Unbalanced Output Switch when inverter work on On-grid state