Watts WFHC 06Z 02 HC RF 24 User Manual Download Page 5

 

3.3  DIP switch configuration (In Orange) 

 

 

 

DIPswitch 

number 

Function

 

Value  

(default: OFF)

 

Configuration 

Description 

DIP1 

Controller 

function 

OFF 

Local Pump 

See 5.3 

  

ON 

Global pump 

DIP2 

Actuator types 

 

OFF 

NC actuator 

See 5.6 

 

ON 

NO actuator  

DIP3 

Pump delays 

(After start / After 

stop request) 

 

OFF 

2min/5min 

See 5.3 

 

ON 

5min/20min 

DIP4 and 

DIP5 

H&C 

switch 

control 

OFF 

OFF 

Central Unit 

BT-CT02 RF 

See 5.2 

 

OFF 

ON 

Master thermostat 

BT-D03 RF 

ON 

OFF 

WFC HCM RF 

ON 

ON 

H&C input 

DIP6 

Anti Grip  

OFF 

Enabled 

See 7.1 

ON 

Disabled 

DIP7 

Humidity 

management 

OFF 

Comfort approach 

See 5.5 

ON 

Safety approach 

DIP8 

Humidity sensor 

OFF 

ON/OFF sensor 

See 5.5 

ON 

Pipe temperature 

sensor 

 

3.4  USB stick 

USB connectivity allows  

 

To update the Software of the controller.  

 

To record data for system monitoring 

 

For the software update, please refer to wattswater.eu for getting the file, put the file on an USB stick. 

 

Insert the USB stick on the controller 

 

Switch OFF/ON the controller 

 

During update,  

o

 

Green LED are power on from Z1 to Z6/Z8 

o

 

All LED become red 

o

 

Red LED are power Off from Z6/Z8 to Z1 

 

After update, you can remove the USB stick 

 

 

 

 

Summary of Contents for WFHC 06Z 02 HC RF 24

Page 1: ...1 Water Floor Controller Wireless Heating Cooling WFHC 06Z 02 HC RF 24 WFHC 06Z 02 HC RF 230 WFHC 10Z 02 HC RF 24 WFHC 10Z 02 HC RF 230...

Page 2: ...2 USER GUIDE GB...

Page 3: ...the installation complies with existing regulations before operation to ensure proper use of the installation 2 PRESENTATION The Connecting box WFC HC RF is especially designed to control your Under F...

Page 4: ...ing mode Pump Drier Led Green Blue Red Fix Green Pump is triggered Red blinking System error security detection humidity sensor error Blue blinking Global humidity detection Blue flashing Humidity con...

Page 5: ...C input DIP6 Anti Grip OFF Enabled See 7 1 ON Disabled DIP7 Humidity management OFF Comfort approach See 5 5 ON Safety approach DIP8 Humidity sensor OFF ON OFF sensor See 5 5 ON Pipe temperature sens...

Page 6: ...central unit as an ON OFF device This solution allows getting a remote control of the H C mode from the application Format of the signal The input could be free contact or live contact 230V Mode Free...

Page 7: ...ng demand and pump output stop is configurable Pump stops 5 minutes after heating or cooling demand stop if DIP switch 3 OFF Pump stops 20 minutes after heating or cooling demand stop if DIP switch 3...

Page 8: ...d is not sent to the main controller 2 Water temperature sensor For each zone the controller computes the dew point based on the ambient temperature and relative humidity sent by each thermostat When...

Page 9: ...ase you need to install the external antenna outside the metallic box Please respect the mounting to optimize sensitivity and avoid any dysfunction Antenna must be installed outside the metallic box i...

Page 10: ...Thermostats Put product in RF pairung mode refer to corresponding instruction manual If RF pairing is done the leds of the channels selected on the WFHC 02 HC RF must turn Green and the thermostats m...

Page 11: ...WFHC 02 HC RF returns to normal mode and the led on the repeater becomes green fix 5 1 2 Multiple controller s installation If there are multiple interconnected controllers in the installation there...

Page 12: ...both WFC H C return to normal mode 5 2 System configuration with central unit The central unit centralizes the communication between controllers Device 1 WFC H C RF Device 2 BT CT02 RF Remarks By pres...

Page 13: ...order to trigger a dehumidifier Device 1 WFHC 02 HC RF Device 2 BT WR02 RF or BT FR02 RF Remarks By pressing for 5 seconds the controller goes in RF pairing menu Bu using and select zone 4 Red led pr...

Page 14: ...d or blue blinking on Heat and Cool led Security detection The contact of the security input is opened If you not using a security thermostat make sure you have installed a strap on the security therm...

Page 15: ...ctrical protection Class II with functional earth IP Protection IP30 Shipping and storage temperature 10 C 50 C 14 F 122 F Power supply 230 Vac 10 50Hz Output maximum load 2 outputs Relay 5A Actuators...

Page 16: ...C RF 24 and WFHC 10Z 02 HC RF 230 Weight xxxxxx 8 DIRECTIVES Designation Description Link Low Voltage Directive LVD The Low Voltage Directive LVD 2014 35 EU ensures that electrical equipment within ce...

Page 17: ...tances Directive RoHS 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electrical and electronic equipment 2011 65 EU Waste Electrical Electronic Equipment Directi...

Page 18: ...leva Str P O Box 55 post office Trakia 4023 Plovdiv Bulgaria T 359 32 605 300 F 359 32 605 301 E mail info wattsindustries bg http wattswater eu Germany Austria and Switzerland Watts Industries Deutsc...

Reviews: