background image

Indice de protection 

 

IP68 

Enclosure protection 

 

Facteur de marche 

 

50% 

Duty cycle 

Anticondensation 

intégrée 

 
 
 
 

Anticondensation 

heater 

VT 

Actionneur électrique 

Manuel d’Installation et d’Utilisation 
Installation and Operation Manual 
Installations- und Bedienungsanleitung 
Manual de instalación y funcionamiento 

FR 

UK 

DE 

ES 

Valpes.com 

Summary of Contents for Valpes VT Series

Page 1: ...he 50 Duty cycle Anticondensation intégrée Anticondensation heater VT Actionneur électrique Manuel d Installation et d Utilisation Installation and Operation Manual Installations und Bedienungsanleitung Manual de instalación y funcionamiento FR UK DE ES Valpes com ...

Page 2: ...on Transport and storage Maintenance Warranty Return of goods Safety instructions Actuators description 14 Dimensions 15 Emergency manual override 15 Electric wiring 16 Warnings Wiring Instructions Electric diagrams Technical data 20 Français 2 English 12 Deutsch 22 Español 32 ...

Page 3: ...ke responsibility for any direct or indirect accidents risks originated by a failure of our products The warranty does not cover the consequences of breakdown and excludes any payments for indemnities The accessories and adaptations are excluded from the warranty In the event that a cus tomer has not proceeded to payments within the agreed period our warranty will be suspended until the delayed pa...

Page 4: ... Description Part Description Part Description 1 Visual position indicator 7 Aluminium support plate 13 Seal 2 Cover 8 O ring 14 Hand wheel 3 Stainless steel screws 9 O ring 15 O ring 4 Terminal strip 10 M20x1 5 threaded open ings 16 O ring 5 Cams 11 Earth screw 17 Cast iron support plate 6 Motor 12 O ring ...

Page 5: ... actuator it is necessary to remove the cover Mounting of the cover appendix p 14 mark 2 make sure that the seal ring appendix p 14 mark 6 is correctly placed in its posi tion grease of the flame path Molydal 3790 grease or equivalent mount the cover and tighten the 4 screws M6 appendix p 14 mark D torque 6Nm Mounting of the position indicator appendix p 14 mark 1 mount the seal ring and the indica...

Page 6: ...oltage The selection of the cables and cable glands the maximal operating temperature of the cables and cable glands must be at least 110 C It is necessary to connect all actuators to an electrical cabinet The power supply cables must have the RATED diameter for the maximum current supported by the actuator and comply with IEC 60227 or IEC 60245 stand ards In order to ensure the IP68 tightness the...

Page 7: ...cam is used to detect the open position FC1 and the black cam is used to detect the closed position FC2 The auxiliary limit switches must be connect with rigid wires If the applied voltage is higher than 42V the user must foresee a fuse in the power supply line Unscrew the right cable gland and insert the cable Remove 25mm of the cable sheath and strip each wire by 8mm Connect the wires to the ter...

Page 8: ...imit switch FCF Close limit switch FC1 Auxiliary limit switch 1 FC2 Auxiliary limit switch 2 C Capacitor F Motor thermoswitch Rep Designation TLO Torque switch opening TLF Torque switch closing H Anti condensation heater M Motor VL Purple MR Brown RG Red NR Black BU Blue OG Orange BC White D1 D2 Failure report terminal 230V AC max 5 A 230V electric diagram The terminal temperature can reach 90 C T...

Page 9: ...Close limit switch TLO Torque switch opening FC1 Auxiliary limit switch 1 FC2 Auxiliary limit switch 2 TLF Torque switch closing BC White F Motor thermoswitch H Anti condensation heater M Motor VL Purple MR Brown RG Red NR Black BU Blue OG Orange D1 D2 Failure report terminal 230V AC max 5 A The motor power supply is wired on bistable three phase relay not delivered If working inverted invert 2 ph...

Page 10: ...o 31 C decreasing linearly to 50 rela tive humidity at 40 C Pollution degree Applicable POLLUTION DEGREE of the intended environment is 2 in most cases Weight 54kg Mechanical data Nominal torque 1200Nm 2000Nm Maximum torque 1500Nm 2400Nm Operating time 90 113s 113s Angular range 90 180 270 on request Duty cycle 50 Drive ISO5211 Star 36 depth 41mm F12 F14 F16 depth F12 20mm F14 25mm F16 30mm Manual...

Reviews: