DSBA3401
·
Rév. 08/08/2020
56
EN
VRX25 VRX45 VRX75
Installation
Proofness
IP68 (5 m 72 h)
Corrosion resistance (outdoor and in-
door use)
Housing: alu epoxy coating (« marine » high durability coating on request)
Drive : Steel + Zn treatment / Axles and screws : Stainless steel
Extended environmental conditions
Outdoor use and in WET LOCATION
Using temperature
Multivolt : -20 °C to +70 °C, 400 V, triphasé : -20 °C to +54 °C
BBPR, GPS and GFS : -10 °C to +40 °C
Altitude
altitude up to 2 000 m
Hygrometry
maximum relative humidity 80 % for temperatures up to 31 °C decreasing linearly
to 50 % relative humidity at 40 °C
Pollution degree
Applicable POLLUTION DEGREE of the intended environment
2 (in most cases)
Weight
4Kg to 4,4kg
Mechanical specifications
Nominal torque
20 Nm
35 Nm
60 Nm
Maximum torque
25 Nm
45 Nm
75 Nm
Operating time (90°)
7s
400 V : 10 s • POSI : 15 s
15 s
400 V : 10 s
20 s
400 V : 15 s
Rotation angle
90° (180°- 270° on request)
Drive ISO5211
star 17mm (depth 19mm)
F05 (depth 15 mm) • F07 (depth 17 mm)
Screws maximal length
F05 : valve connection plate 10mm
F07 : valve connection plate 12mm
Manual override
Axe sortant
Electrical specifications
Voltage
1)
(standard)
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
15 V to 30 V AC 50/60 Hz and 12 V to 48 V DC
3-phase 400 V 50/60 Hz
Voltage
1)
(GP5 and GF3)
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
15 V to 30 V AC 50/60 Hz and 12 V to 48 V DC
Voltage
1)
(GP6, GPS and GFS)
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC
Overvoltage category
2)
TRANSIENT OVERVOLTAGES up to the levels of OVERVOLTAGE CATEGORY ll
TEMPORARY OVERVOLTAGES occurring on the MAINS supply.
Power consumption
45 W (400 V : 52 W)
Insulation motor class
Class B 400V motors and class F for the others
Torque limiter
Electronical
Operating factor
50 %
Number of feedback switches
2 (4 optional)
Limit switches maximal voltage
4 to 250V AC/DC (Overvoltage category II)
Limit switches maximal current
1mA to 5A max
Inrush current
Circuit breaker type D, nominal current according the number of actuators
Anticondensation resistor
10 W
ATEX marking
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006 X • T
a
= -20 °C to +70 °C
ATEX marking (3-phase 400 V)
II 2 G D Ex db IIB T5 Gb Ex tb IIIC T95 °C Db LCIE 06 ATEX 6006 X • T
a
= -20 °C to +54 °C
ATEX marking (GS6, GPS and GFS)
II 2 G D Ex db IIB T6 Gb Ex tb IIIC T80 °C Db LCIE 06 ATEX 6006 X • T
a
= -10 °C to +40 °C
1)
The actuator tolerates voltage fluctuation of the electrical grid up to ± 10 % of its nominal system operating voltage
2)
The actuator tolerates temporary overvoltages of the electrical grid.