1. Expansion Valve and Temperature Pressure Relief Valve drain line diameter must  
     be no smaller than the nominal size of the valve outlet.
2. Drain line length must be in accordance with this table:

Maximum Relief Drain 
Length (m)

Maximum Numbers of 
Changes in Direction (greater 
than 45°)

9

3

8

4

7

5

6

6

3. Drain line must discharge into a tundish when the distance to the final point of  
     discharge is greater than 9 m.
4. Drain Line must be of copper piping
5. If Expansion Valve and Temperature Pressure Relief Valve drain lines are to be  
    combined then refer to AS/NZ 3500.4:2015 Clause 5.11.3. Only one of each type to  
    be combined.