background image

Snow Sensor 095

Installation & Operation Manual

095_D

11/17

Snow Melting Replaces: 05/13

© 2017 tekmar  095_D - 11/17

Installation & Operation Manual

The Snow Sensor 095 is an aerial mounted sensor that detects falling snow and 

allows a tekmar Snow Melting Control to automatically start the snow melting 

equipment. System stop is provided by the control’s timer or by manual disable. 

The 095 mounts to a nominal 1/2” (16 mm) metal or PVC conduit or pole. The 095 

is well suited for adding automatic start to an existing snow melt system.

For use with tekmar Snow Melting Control type: 654, 670 or 680

Introduction

Snow

Sensor

095

Summary of Contents for Tekmar WiFi Snow Melting Control 670

Page 1: ...ng snow and allows a tekmar Snow Melting Control to automatically start the snow melting equipment System stop is provided by the control s timer or by manual disable The 095 mounts to a nominal 1 2 1...

Page 2: ...d contact your wholesaler or tekmar sales representative for assistance Type 095 includes One Snow Sensor 095 One Installation and Operation Manual 095_D Step 2 Choosing a Location for the Sensor The...

Page 3: ...ded cable one end of the shield wire should be connected to the Com terminal on the Snow Melting Control and the other end should remain free The shield must not be connected to earth ground 1 Remove...

Page 4: ...ntrols com Step 6 Mounting The conduit pole can be either PVC plastic or rigid metal The conduit pole should be mounted plumb using a level When using PVC plastic conduit a nominal 1 2 16mm PVC male t...

Page 5: ...300 000 Ohms 3 Measure the resistance between the red RED and black BLK wiring terminals This reading should be between 45 to 47 Ohms If resistance readings are outside of the normal operating range t...

Page 6: ...2 29 996 40 4 26 099 45 7 22 763 50 10 19 900 55 13 17 436 60 16 15 311 65 18 13 474 70 21 11 883 75 24 10 501 80 27 9 299 85 29 8 250 Temperature Resistance F C 90 32 7 334 95 35 6 532 100 38 5 828 1...

Page 7: ...0 4 lbs 180 g Dimensions 1 15 16 H x 3 5 32 O D 50 H x 80 O D mm Enclosure White PVC plastic UV stable NEMA type 1 Operating range 40 to 122 F 40 to 50 C Compatible equipment tekmar Snow Melting Contr...

Page 8: ...r labor to remove or transport the defective Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s agreement and warranty with its custom...