4
IOM-T-560 2145
© 2021 tekmar
Tools Required
• tekmar or jeweler screwdriver
• Phillips head screwdriver
• Wire stripper
• Drill (for wall anchor)
• 3/16" drill bit (for wall anchor)
Materials Required
• 18 AWG LVT Solid Wire (Low Voltage Connections)
Consider the following:
• Interior Wall.
• Keep dry. Avoid potential leakage onto the control.
• Relative Humidity less than 90%. Non-condensing environment.
• No exposure to extreme temperatures beyond 32-122°F (0-50°C).
• No draft, direct sun, or other cause for inaccurate temperature readings.
• Away from equipment, appliances, or other sources of electrical interference.
• Easy access for wiring, viewing, and adjusting the display screen.
• Approximately 5 feet (1.5 m) off the finished floor.
• The maximum length of wire is 500 feet (150 m).
• Strip wire to 3/8" (10 mm) for all terminal connections.
• Use standard 8 conductor, 18 AWG wire.
Preparation
Installation Location
NOTICE
Installation