Setting
Range
Default
ROOM HOT WARNING
Displays error on home screen if the room exceeds this tem-
perature.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
ROOM COLD WARNING
Displays error on home screen if the room falls below this tem-
perature.
Off, 40 to 100°F
Off, 4.5 to 38.0°C
Off
Setting
Range
Default
SENSOR 1
Select the type of sensor connected to S1 and Com wiring
terminals.
Off,
Room,
Floor
Off
SENSOR 2
Select the type of sensor connected to S2 and Com wiring
terminals.
Off,
Room,
Floor,
Outdoor
Off
INTERNAL ROOM SENSOR
Select if the internal room temperature sensor is on or off. Only
available when Sensor 1 or 2 is set to read a room or floor sen-
sor.
Off,
On
On
ROOM OFFSET
Select if the internal room temperature sensor is on or off. Only
available when Sensor 1 or 2 is set to read a room or floor sen-
sor.
Off,
-5 to +5°F
-3.0 to 3.0°C
Off
FLOOR OFFSET
Manual offset correction of the floor temperature measurement.
Off,
-5 to +5°F
-3.0 to 3.0°C
Off
Setting
Range
Default
RADIANT FLOOR HEATING
Select if the first stage W1 heats a radiant floor.
No,
Yes
No
Setup - Sensors
Setup - Alerts