Display
Setting
Installer settings. Press the
and
buttons together for 5 more seconds.
AUXILIARY SENSOR
Select the type of auxiliary sensor. Available when an auxiliary
sensor is automatically detected.
NONE
= no auxiliary sensor,
ROOM
= Indoor Sensor,
OUT
= Outdoor Sensor,
FLOR
= Slab
Sensor
Room
ROOM SENSOR
Select if the built-in room temperature sensor is on or off. The built-
in room sensor can only be disabled when an auxiliary room or slab
sensor is connected.
F
MAX
FLOOR MAXIMUM
Set the floor maximum temperature in order to protect the floor
covering. Suggested settings: Tile = 90°F (32°C), Wood Floor =
85°F (29°C)
F
SET AWAY
Set the away temperature.
ESCAPE
Release the and buttons to return to the home screen.
For a full list of settings and operational details, please refer to the thermostat
Installation and Operation Manual 518_D that is available from tekmarControls.com
518_Q - 06/16