17
Menus
Home Screen
Parameter
Range
Description
HOME SCREEN
CONDENSATE
-32 to 266°F
(-55 .0 to 65 .0°C)
The condensate return temperature .
OUTDOOR
-67 to 149°F
(-35 .0 to 130°C)
The outdoor air temperature .
TARGET
100 to 220°F
(38 .0 to 104 .5 °C)
The condensate return must reach the steam established target to the Heat On cycle .
PRESSURE
0 .0 to 15 .0 psi
(0 to 105 kPa)
The steam system pressure .
TIME REMAINING
(HEAT ON)
00:00:00 to
02:00:00
The time that the boiler is on during the heating cycle .
TIME REMAINING
(HEAT OFF)
00:00:00 to
02:00:00
The time that the boiler is off during the heating cycle .
SYSTEM INPUTS
ROOM TARGET
35 to 100°F
(1 .5 to 38 .0°C)
The desired room temperature when an indoor sensor is installed .
BOOST
Off or On
Dot is green when Boost is active .
EARLY START
Off or On
Dot is green when Early Start is active .
SMART SETBACK
Off or On
Dot is green when Smart Setback is active .
DOMESTIC HOT
WATER
Off or On
Dot is green when DHW call is active .
OUTDOOR
-67 to 149°F
(-35 .0 to 130°C)
The outdoor air temperature .
CONDENSATE
-32 to 266°F
(-55 .0 to 65 .0°C)
The condensate return temperature .
INDOOR
35 to 100°F
(1 .5 to 38 .0°C)
The indoor sensor temperature .
PRESSURE
1 .0 to 15 .0 psi
(0 to 105 kPa)
The steam system pressure .
SYSTEM STATUS
COMBUSTION AIR
Off or On
Dot is green when combustion air damper is open .
WARM WEATHER
SHUT DOWN
Off or On
Dot is green when warm weather shut down is in effect .
OVERRIDE
Auto, Hand, Max
Heat, Off
The manual override status .